HP UPS Network Module User Manual

Page 43

Advertising
background image

HP UPS Network Module web interface 43

To add a trap receiver:

1.

Click Add Trap Receiver.

2.

Configure the settings for the new application on the Trap Receivers Settings screen (on page

44

).

To modify a trap receiver:

1.

Select the checkbox for the application you want to modify. To select all applications, click All.

2.

Click Modify Trap Receiver.

3.

Modify the settings for the application on the Trap Receivers Settings screen (on page

44

).

To remove a trap receiver:

1.

Select the checkbox for the application you want to remove. To select all applications, click All.

2.

Click Remove.

To simulate a utility power failure:

1.

Select the checkbox for the application you want to test. To select all applications, click All.

2.

Click Utility Failure Test. The UPS Network Module sends a Utility failure trap, and then sends a Utility
restored trap 30 seconds later.

3.

Verify that the selected application received the traps over the network.

To simulate a UPS On Battery condition:

1.

Select the checkbox for the application you want to test. To select all applications, click All.

2.

Click Shutdown Test.

3.

The selected application processes the simultaneous alarms and performs an actual shutdown
sequence.

CAUTION:

The Shutdown Test generates an actual shutdown sequence for the server on which

the application is running.

4.

Verify that the server protection is working correctly.

Click Help to view online help.