Management module 33

Management module

Management module overview

The HP mc-Series 5042 Rack has a management module, which can be accessed remotely through the web
interface. The management module analyzes, queries, and manages various measurements and warning

and alarm messages from the unit.
The management module (on page

33

) analyzes measurements provided by each sensor or module,

generates any necessary warning or alarm messages, and then sends them to the web interface. When a
new warning or alarm occurs, the warning and alarm messages (on page

48

) appear on the operator

display as well as on the web interface Alarms menu and Alarm History menu. An alarm relay is also

activated (if installed on the unit and enabled in the appropriate web interface menu), and an audible alarm

is signaled by the internal beeper (if enabled in the appropriate web interface menu).
The management module performs regulation operations such as:

Retrieving all measurements from the fan units and the water units in cycles, approximately once per

second (temperature, fan speed, and chilled water flow rate)

Analyzing all measurements and generated alarm and warning messages

Calculating heat removed from the water flow rate and temperature of the water supply and return

Measuring water flow rate

Regulating the server air inlet temperature by controlling the water flow

Sending control settings for fan speeds back to the MCS 5042 unit

Sending various system values to the web interface

The web interface displays various measurements and warning and alarm messages (on page

48

) from the

management module. Also, various system values can be set through the web interface and sent to the
management module. For more information about the web interface, see the HP mc-Series 5042 Rack Web

Interface User Guide.
The following values can be set through the web interface and sent to the management module:

Server Intake Temperature Set Point—Target value used by the management module for server intake
regulation

High Temperature Threshold—Temperature difference above Server Intake Temperature Set Point for
temperature-critical alarm message

Warning Temperature Threshold—Temperature difference above Server Intake Temperature Set Point
for temperature warning message

Low Temperature Threshold—Temperature difference below Server Intake Temperature Set Point for
temperature warning message

The following values are displayed in the web interface for information only:

Fan Speed—Displays the fan speed percentage

Water Valve—Displays the water valve state