Water quality requirements and specifications, Acceptable water quality specifications – HP Modular Cooling System User Manual

Page 63

Advertising
background image

Water quality and leveling requirements, and condensation management 63

Water quality and leveling requirements, and
condensation management

Water quality requirements and specifications

Closed-loop water must not contain any lime scale deposits or loose debris. The water must have a low level

of hardness, particularly a low level of carbon hardness. Filters must be used to remove free floating

particulates and be regularly maintained. Additionally, the water must not be so soft that it attacks the

materials with which it comes into contact. You must periodically add new fresh water, but also to remove

some enriched water. HP recommends a #30 mesh filter is recommended for filtering water entering the MCS
5042 unit and a 1 µm filter for prolonged performance.
Also consider the required set point for the water temperature. Temperatures near or below 0ºC (32ºF) mean

that the chilled water plant condenser is very close to or below the freezing point of the water. The chilled

water temperature to be supplied to the MCS 5042 unit is 5ºC (41ºF). Freezing water can cause a blockage
and damage to the unit. Therefore, an additive such as glycol might be necessary to lower the freezing point.

However, the heat transfer potential of the water is lower, so the equipment must be derated properly.
In a cooling loop, metallic materials in a pipe distribution network are in constant contact with recirculating

liquid and can react with impurities to cause corrosion that can develop into leaks or form deposits and
blockages.
The rate of galvanic corrosion depends on the electrical potential between the two dissimilar metals and the

temperature of the liquid.
A 10-degree increase in water temperature can double the rate of corrosion.
For more information, see the HP mc-Series 5042 Rack Site Preparation Guide on the HP website

(

http://www.hp.com

).

Acceptable water quality specifications

The following values are water quality ranges required for continuous quality of performance.

Parameter

Range

pH

7-9

Specific conductance at 25ºC (77ºF) <2500 µmhos
Sulfur (SO

4

), total

<100 ppm

Chloride (Cl)

<50 ppm

Sulfide (S)

<10 ppm

Hardness (CaCO

3

), total

<200 ppm

Iron (Fe), total

<3.0 ppm

Manganese (Mn), total

<0.1 ppm

Bacteria

<1000 CFUs/ml

Residue on evaporation

<500 ppm

Turbidity

20

Advertising