HP Modular Cooling System User Manual

Page 53

Advertising
background image

Operator display 53

Temperature below threshold (Low Temperature Threshold field)

Indicators

Meaning

Operator display alarm message Temperature too low

Web interface alarm message

Temperature too low

Condition

The average server air temperature is lower than the temperature assigned
in the web interface Intake Temp tab Low Temperature Threshold field.

Sensors

Air temperature sensor

SNMP notification

Warning

Type of message

Warning

Solution:

1.

Verify water flow matches specifications required for heat load.

2.

Verify whether the water temperature is below the expected range.

3.

Adjust the temperature assigned in the web interface Intake Temp tab Low Temperature Threshold field.

4.

Contact your building supervisor.

Temperature above threshold (Warning Temperature Threshold field)

Indicators

Meaning

Operator display alarm message Temperature Warning

Web interface alarm message

Temperature Warning

Condition

Average server air temperature is above the temperature assigned in the

web interface Intake Temp tab Warning Temperature Threshold field

Modules or sensors

Air temperature sensor

SNMP notification

Warning

Type of message

Warning

Solution:

1.

Verify water flow matches specifications required for heat load.

2.

Verify whether the water temperature is above the expected range.

3.

Adjust the temperature assigned in the web interface Intake Temp tab Warning Temperature Threshold
field.

4.

Contact your building supervisor.

Emergency Door Opening due to Water Flow Loss (0 l/min; 36/34/35°C) (0 gal/min; 97/93/95°F)

Indicators

Meaning

Operator display alarm message Emergency Door, Flow

Web interface alarm message

Emergency Door Opening due to Water Flow Loss (0 l/min; 36/34/35°C)

(0 gal/min; 97/93/95°F)
The interface alarm message displays the temperatures of the fans so that

you can see which temperature has been exceeded and caused the alarm.

Condition

The water flow loss emergency door opening temperature threshold has

been exceeded or the water flow is less than 2 l/min (.5283 gal/min).

Modules or sensors

Server Intake Temperature, Water Flow Meter

Advertising