Connecting water to the facility – HP Modular Cooling System User Manual
Page 24

Installation 24
12.
(Optional, but HP-recommended) To set up your SNMP managers, click Setup>Management>SNMP
Managers.
13.
Click Save Settings.
For more information on adjusting the management module settings through the web interface, see the HP
Modular Cooling System Web Interface User Guide.
Connecting water to the facility
CAUTION:
Before attaching the hoses to the MCS-100 unit, verify that the water supply and
return are closed. Water that leaks into the unit can cause significant damage.
CAUTION:
Do not over tighten the connection. Tightening the connection too much might
damage the gaskets.
NOTE:
The MCS-100 unit is equipped with a failed-open control valve. For water to flow through
the unit without restrictions during the initial water hook up, HP recommends that the control valve
is set manually to Open through the web interface.