Operator display, Operator display overview, Operator display components – HP Modular Cooling System User Manual

Page 43: Warning and alarm messages

Advertising
background image

Operator display 43

Operator display

Operator display overview

The operator display provides information on the system operation, viewable on the outside of the MCS-100

front door. When the management module issues an alarm or warning, the warning and alarm messages
display ("

Warning and alarm messages

" on page

43

) on the operator display, as well as on the web

interface Alarms menu and Alarm History menu.

Operator display components

The operator display on the front door of the MCS-100 unit has a digital touch-screen.
To scroll through the menu options, press the appropriate button on the bottom of the screen.

Warning and alarm messages

The following tables describe the possible warning and alarm messages that the MCS-100 unit sends to the
management module. These messages appear on the operator display and on the web interface Alarms

menu and Alarm History menu.
Fan unit failed or not installed

Indicators

Meaning

Operator display alarm message Fan 1, 2, 3, or 4 Failed

Web interface alarm message

Fan 1, 2, 3, or 4 Failed or Not Installed

Condition

Fan 1, 2, 3, or 4 is running at less than the minimum RPM

Sensors

Fan 1, 2, 3, or 4

SNMP notification

Warning

Advertising