Management module components – HP Modular Cooling System User Manual

Page 30

Advertising
background image

Management module 30

•

Fan Module—Displays the Server Intake and Server Exhaust Temperature as well as the RPM of each

fan

•

Water Inlet Temperature—Displays the temperature of the water coming into the MCS-100 unit to be

used to cool the servers

•

Water Outlet Temperature—Displays the temperature of the water after removing the server heat

•

Water Flow—Displays the value of the water flow in liters/gallons per minute

Management module components

The management module is located on the lower front of the MCS-100 unit, behind the front door.

Item Reference

Description

1

C key

Used to confirm warnings, critical alarms, and
configuration setting changes, as well as to turn off the
audible alarm. To confirm these situations, press and

hold the C key for five seconds, or click the Clear Alarms
button on the Setup tab>General menu on the web
interface.

2

Power/alarm LED Used to indicate the internal status of the management

module, and to signal warnings and critical alarms.

•

If the LED is green, the management module has

power, and conditions are normal.

•

If the LED is green and blinking, communication is

taking place.

•

If the LED is yellow, a warning has been issued.

•

If the LED is red, a critical alarm has been issued.

•

If the LED is blinking green, yellow and red, then a

configuration setting change has been made. To save

the new configuration settings to the internal memory
of the management module, press and hold the C key
for five seconds.

•

If the LED is off, the management module has no

power.

3

Mini USB
connection

Used for USB connections for initial setup.