HP PDR Management Module web interface 43

ModBus registers

If trying to query the PDR management module, list out the following menu to be queried.
The ModBus Register address is based on offset -1.
Use function code 04h to read the analog input registers.
PDR ModBus input registers (16-bit) include:

Register Name

Panel Breaker Count Format Units

1001 Module

Manufacturer - -

32 STRING -

1033 Module

Model

- -

32 STRING -

1065

Module Firmware Version

-

-

32

STRING

-

1097

Module Hardware Version

-

-

32

STRING

-

1129 Module

Name

- -

32 STRING -

1161

Module Part Number

-

-

32

STRING

-

1193

Module Serial Number

-

-

32

STRING

-

1225

Module MAC Address

-

-

32

STRING

-

1257 Manufacturer

- -

32 STRING -

1289 Model

- -

32 STRING -

1321 Software

Version

- -

32 STRING -

1353 Name

- -

32 STRING -

1385 Part

Number

- -

32 STRING -

1417 Serial

Number

- -

32 STRING -

1449

Nominal Output Volts

-

-

1

UNIT16

0.1 V

1450 Reserved

- -

1 -

-

1451

Nominal Output Frequency

-

-

1

UNIT16

0.1 Hz

1452 Max

Panels

- -

1 UNIT16 -

1453 Panels

Configured

- -

1 UNIT16 -

1454 Panels

Live

- -

1 UNIT16 -

1455 Live

Panels

List

- -

8 UNIT16 -

1463 Panel

Monthly

KWH

1 -

2 UNIT16 0.01

KWH

1465

Panel Yearly KWH

1

-

2

UNIT16

0.01 KWH

1467

Panel Total KWH

1

-

2

UNIT16

0.01 KWH

1469 Panel

Config

1 -

2 UNIT16 2

1471 Reserved

1 -

1 -

-

1472

Panel Breaker Rating

1

-

1

UNIT16

0.1 A

1473

Panel Breaker Warning

1

-

1

UNIT16

0.1%

1474

Panel Breaker Overload

1

-

1

UNIT16

0.1%

1475 Reserved

1 -

1 -

-

1476 Reserved

1 -

1 -

-

1477 Reserved

1 -

10 -

-

1487 Reserved

1 -

10 -

-