Troubleshooting 58

-or-

Click Continue to this website (not recommended) to ignore the security warning.

Error LED illuminates or flashes

Action: Press the Reset button on the management module front panel. If the problem persists, contact an
authorized service provider.
The following table lists the error conditions associated with the management module LED.

Test

LED flash error code

Description

1

Permanently on

DRAM failure

2

2 flashes

DMA Mem to Mem error

3

3 flashes

IRQ error

4

4 flashes

Ethernet error

5

5 flashes

Serial loop back error

6

6 flashes

RTC error

FTP error messages appear when connecting

through Linux

Symptom: When connecting to FTP through Linux, error messages about bad commands appear.
Action: The user can log in although the error messages appear.

Flash update fails over a serial connection

Action: Disable any serial port being configured during the flash update, such as iLO, or use an FTP

connection.

HP SIM lists a discovered PDR as Unmanaged in the

System Type column

Action:

1.

Delete the discovered PDR from HP SIM.

2.

Using the management module web interface, add the HP SIM server as a Manager on the SNMP
Managers tab (on page 38).

3.

Rediscover the PDR in HP SIM.

LCD configuration matches the panel breaker ratings

Possible Cause: The LCD configuration menu in the breaker panel rating is mismatched.