HP ProLiant DL388e Gen8 Server User Manual

Page 118

Advertising
background image

Specifications 118

Rated input frequency

50 Hz to 60 Hz

Rated input current

4.1 A

Maximum rated input power

803 W at 200 V AC input

798 W at 240 V AC input

Btu per hour

2739 at 200 V AC input
2735 at 208 V AC input

2731 at 220 V AC input

2728 at 230 V AC input
2724 at 240 V AC input

Power supply output

Rated steady-state power

750 W at 200 V to 240 V AC input

Maximum peak power

750 W at 200 V to 240 V AC input

HP 750 W CS -48 V DC Hot-plug Power Supply (94% efficiency)

Specification

Value

Input requirements

Rated input voltage

-36 V DC to -72 V DC

-48 V DC nominal input

Rated input current

23 A at -36 V DC input

17 A at -48 V DC input, nominal
input

11 A at -72 V DC input

Rated input power (W)

815 W at -36 V DC input
805 W at -48 V DC input, nominal

input

795 W at -72 V DC input

Btu per hour

2780 at -36 V DC input
2740 at -48 V DC input, nominal

input

2720 at -72 V DC input

Power supply output

Rated steady-state power (W) 750 W
Maximum peak power (W)

750 W

CAUTION:

This equipment is designed to permit the connection of the earthed conductor of the

DC supply circuit to the earthing conductor at the equipment.

If this connection is made, all of the following must be met:

This equipment must be connected directly to the DC supply system earthing electrode

conductor or to a bonding jumper from an earthing terminal bar or bus to which the DC supply

system earthing electrode conductor is connected.

This equipment must be located in the same immediate area (such as adjacent cabinets) as any

other equipment that has a connection between the earthed conductor of the same DC supply

circuit and the earthing conductor, and also the point of earthing of the DC system. The DC

system must be earthed elsewhere.

The DC supply source is to be located within the same premises as the equipment.

Switching or disconnecting devices must not be in the earthed circuit conductor between the

DC source and the point of connection of the earthing electrode conductor.