Hot-plug power supply calculations – HP ProLiant DL388e Gen8 Server User Manual

Page 119

Advertising
background image

Specifications 119

CAUTION:

To reduce the risk of electric shock or energy hazards:

This equipment must be installed by trained service personnel, as defined by the NEC and IEC

60950-1, Second Edition, the standard for Safety of Information Technology Equipment.

Connect the equipment to a reliably grounded SELV source. An SELV source is a secondary

circuit that is designed so normal and single fault conditions do not cause the voltages to
exceed a safe level (60 V DC).

The branch circuit overcurrent protection must be rated 24 A.

HP 1200 W CS Platinum Plus Hot-plug Power Supply (94%

efficiency)

Specification

Value

Input requirements

Rated input voltage

100 V AC

110 V AC to 120 V AC

200 V AC to 240 V AC

Rated input frequency

50 Hz to 60 Hz

Rated input current

9.1 A at 100 V AC

8.6 A at 110 V AC

6.7 A at 200 V AC

Maximum rated input power

897 W at 100 V AC input
1321 W at 200 V AC input

Btu per hour

3061 at 100 V AC input

4506 at 200 V AC input

Power supply output

Rated steady-state power

800 W at 100 V AC input
900 W at 120 V AC input

1200 W at 200 V to 240 V AC

input

Maximum peak power

800 W at 100 V AC input
900 W at 120 V AC input

1200 W at 200 V to 240 V AC

input

Hot-plug power supply calculations

For hot-plug power supply specifications and calculators to determine electrical and heat loading for the
server, see the HP Power Advisor website (

http://www.hp.com/go/hppoweradvisor

).