Advance Planning

DUCT FITTINGS

This Hood Must Use an

8" Round Duct. It Can

Transition to a

3-1/4" x 12" Duct.

Use this chart to compute

maximum permissible lengths for

duct runs to outdoors.

NOTE: Do not exceed maximum

permissible equivalent lengths!

Maximum duct length:

100 foot for range hoods.

Flexible ducting:
If flexible metal ducting is used,

all the equivalent feet values

in the table should be doubled.

The flexible metal duct should

be straight and smooth and

extended as much as possible.

DO NOT use flexible plastic

ducting.

NOTE: Any home ventilation

system, such as a ventilation

hood, may interrupt the proper

flow of combustion air and

exhaust required by fireplaces,

gas furnaces, gas water heaters

and other naturally vented

systems. To minimize the chance

of interruption of such naturally

vented systems, follow the heating

equipment manufacturer’s

guidelines and safety standards

such as those published by NFPA

and ASHRAE. When applicable,

install any makeup (replacement)

air system in accordance with local

building code requirements. Visit

GEAppliances.com for available

makeup air solutions.

Total

Equivalent

Quantity

Equivalent

Duct Piece

Dimensions

Length*

Used

Length

Round,

1

ft.

straight

(per

foot

length)

3-1/4" x 12"

1 ft.

straight

(per

foot

length)

90°

elbow

17

ft.

45°

elbow

10

ft.



ø[

90° elbow

43 ft.

3-1/4" x 12"

45° elbow

26 ft.

3-1/4"

x

12"

90° flat elbow

102 ft.

8" round to

3-1/4" x 12" transition

2 ft.

3-1/4" x 12" to 8"

round transition

5 ft.

8"

round

to 3-1/4" x 12"

transition 90° elbow

6 ft.

3-1/4" x 12" to 8"

round transition 90° elbow 13 ft.

Round

wall

cap

with damper

32 ft.

3-1/4" x 12" wall cap

with damper

75 ft.

Round

roof cap

44 ft.

Total Duct Run

* Actual length of straight duct plus duct fitting

equivalent. Equivalent length of duct pieces are

based on actual tests conducted by GE Evaluation

Engineering and reflect requirements for good

venting performance with any ventilation hood.