Connections and Wiring

20

NI-700 & NI-900 Hardware Reference Guide

Input/Output (I/O) Port: Connections and Wiring

The I/O port responds to either switch closures, voltage level (high/low) changes, or it can be used for
logic-level outputs. You can connect up to four devices to the NI-700 or NI-900 (FIG. 7).

A contact closure between the GND and an I/O port is detected as a Push.

When used for voltage inputs, the I/O port detects a low signal (0 - 1.5 VDC) as a Push, and a

high signal (3.5 - 5 VDC) as a Release (this IO port uses 5V logic but can handle up to 12V
without harm).

When used for outputs, the I/O port acts as a switch to GND and is rated for 200 mA @
12 VDC. This device can use up to 4 I/O ports (see table below).

The PWR pin provides +12 VDC @ 200 mA and is designed as a power output for the PCS
Power Current Sensors, VSS2 Video Sync Sensors (or equivalent).

The GND connector is a common ground and is shared by all I/O ports. A common ground is

shared with I/O ports 1 - 4 (see table below).

FIG. 7

INPUT/OUTPUT connector (male)

I/O Port Wiring Specifications

Pin

Signal

Function

1

GND

Signal GND

2

I/O 1

Input/Output

3

I/O 2

Input/Output

4

I/O 3

Input/Output

5

I/O 4

Input/Output

6

12 VDC

PWR

Port 4 on the NI-700

Port 5 on the NI-900