Installing the new water heater (cont’d), Venting, Warning – State PR6 75 XRVIT User Manual

Page 15

Advertising
background image

Installing the New Water Heater (cont’d)

15

3

″ PVC, ABS OR CPVC

SCHEDULE 40

90° STREET ELBOW

3

″ PVC, ABS OR CPVC

SCHEDULE 40 PIPE

VENT CAP

WITH SCREEN

3

1

2

'

STRAPPING

Horizontal runs must be securely supported at 3

1

2

foot

intervals and vertical runs supported at 5 foot intervals.

VENTING THROUGH AN OUTSIDE WALL

75 GALLON 70,000 and 75,000 BTU/HR, 50 GALLON

52,500, 55,000 and 62,500 BTU/HR, 40 GALLON 50,000

BTU/HR MODELS ONLY

(See rating plate for BTU/HR rating)

3

PVC, ABS or CPVC Schedule 40 vent piping:

1. A 3

″ PVC Schedule 40-45° vent cap with wire screen is

supplied with the water heater.

2. A 3

″ PVC, ABS or CPVC Schedule 40-90° street ell; used

to connect the vent pipe to the water heater when the

vent pipe is to be turned horizontally directly off the

blower (supplied locally).

3. 3

″ PVC, ABS or CPVC Schedule 40 pipe (must be sup-

plied locally).

The combustion and ventilation air flow must not be

obstructed.

Venting

All vent gases must be completely vented to the outdoors of

the structure (dwelling).

Min. rise

1

8

per five feet

WARNING

To insure proper venting of this gas-fired water heater, the

correct vent pipe diameter must be utilized. Do not install

any other gas appliances on the same vent with this water

heater as this will adversely affect the operation of the

water heater.

WARNING

The water heater outlet must be connected to a vent

which terminates to the outdoors. Never operate the

water heater unless it is vented to the outdoors and has

adequate air supply to avoid risks of improper opera-

tion, explosion or asphyxiation.

WARNING

Be sure vent pipe is properly connected to prevent escape of

dangerous flue gases which could cause deadly asphyxiation.

WARNING

Chemical vapor corrosion of the flue and vent system

may occur if air for combustion contains certain chem-

ical vapors. Spray can propellants, cleaning solvents,

refrigerator and air conditioner refrigerants, swimming

pool chemicals, calcium and sodium chloride, waxes,

bleach and process chemicals are typical compounds

which are potentially corrosive.

WARNING

Obstructed or deteriorated vent systems may present

serious health risk or asphyxiation.

WARNING

The vent pipe from the water heater must slope upward

1

8

inch per five linear feet for any horizontal run.

WARNING

Failure to have required clearances between water heater

and combustible material will result in a fire hazard.