HIGH TEMPERATURE LIMIT SWITCH

(Single-Use Type Energy Cut Off)

The thermostat has a built-in limit switch which will actu-

ate in case of excessive water temperatures. The heater can-

not be relit until the gas control valve is replaced. It is

important that a serviceman be called to determine the rea-

son for limit operation and thus avoid repeated thermostat

replacement. Lower the temperature adjustment setting on

new control.

NOT ENOUGH OR NO HOT WATER

1. Check the manual gas shut off valve to be sure it is open.

2. The ON/OFF switch on the control box must be “ON”.

3. The temperature button adjustment may be set too low.

See the “Temperature Regulation” section.

4. The gas company can check the gas input to see if it is

correct. An underfired water heater will not heat water as

quickly.

5. Look for leaking or open hot water faucet’s. Make sure

all are closed.

6. The cold water inlet temperature may be colder during

the winter months. It will take longer to heat the water

and seem like less hot water.

7. If you cannot find what is wrong, call the local gas util-

ity and/or plumbing contractor.

WATER IS TOO HOT

1. The temperature adjustment setting may be set too high.

See the “Temperature Regulation” section.
NOTE: A period of time is necessary after an adjust-

ment has been made for the water temperature to

reach the new temperature setting.

2. If lower temperature settings will not lower the water

temperature, call the local gas utility.

For Your Information (cont’d)

SMELLY WATER (cont’d)

If the smelly water persists after the anode replacement and

chlorination treatment, we can only suggest that continuous

chlorination and filtering conditioning equipment be con-

sidered to eliminate the water problem.

Do not remove the anode leaving the tank unprotected. By

doing so, all warranty on the water heater tank is voided.

“AIR” IN HOT WATER FAUCET’S

30

VENTING MANUAL RESET SWITCH

There is a venting manual reset switch located on the draft

hood. If the venting manual reset switch is activated, it will

not reset itself. Before resetting this venting manual reset

switch, check for flue blockage and propriety of the venting

system. To reset the venting manual reset switch, press the

red reset button.

BLOWER

MOTOR

VENTING MANUAL

RESET SWITCH

DRAFT HOOD

WARNING

HYDROGEN GAS: Hydrogen gas can be produced in a

hot water system that has not been used for a long peri-

od of time (generally two weeks or more). Hydrogen gas

is extremely flammable and explosive. To prevent the

possibility of injury under these conditions, we recom-

mend the hot water faucet be opened for several minutes

at the kitchen sink before any electrical appliances which

are connected to the hot water system are used (such as

a dishwasher or washing machine). If hydrogen gas is

present, there will probably be an unusual sound similar

to air escaping through the pipe as the hot water faucet is

opened. There must be no smoking or open flame near

the faucet at the time it is open.

WARNING

Should overheating occur or the gas supply fail to shut

off, turn “off” the manual gas control valve to the

appliance.

OR

VENTING MANUAL

RESET SWITCH