SEDIMENT TRAP

A sediment trap shall be installed as close to the inlet of the

water heater as practical at the time or water heater instal-

lation. The sediment trap shall be either a tee fitting with a

capped nipple in the bottom outlet or other device recog-

nized as an effective sediment trap. If a tee fitting is used, it

shall be installed in conformance with one of the methods

of installation shown.

Connecting the gas piping to the gas control valve of the

water heater can be accomplished by either of the two

methods shown.

Installing the New Water Heater (cont’d)

WARNING

The appliance and its gas connection must be leak tested

before placing the appliance in operation.

WARNING

Use pipe joint compound or teflon tape marked as being resis-

tant to the action of petroleum [Propane (L.P.)] gases.

WARNING

Contaminant’s in the gas lines may cause improper

operation of the gas control valve that may result in fire

or explosion. Before attaching the gas line be sure that

all gas pipe is clean on the inside. To trap any dirt or

foreign material in the gas supply line, a drip leg (some-

times called a sediment trap) must be incorporated in

the piping. The drip leg must be readily accessible.

Install in accordance with the “Gas Piping” section.

Refer to the current edition of the National Fuel Gas

Code, ANSI Z223.1, also referred to as NFPA 54.

GAS PIPING WITH FLEXIBLE CONNECTOR

GAS PIPING WITH ALL BLACK IRON PIPE

TO GAS CONTROL

GROUND JOINT

UNION (OPTIONAL)

MANUAL

SHUTOFF

VALVE

GAS

CONTROL

VALVE

GAS SUPPLY PIPING

FLEXIBLE GAS CONNECTOR

LABELED AS COMPLYING

WITH ANSI STANDARDS

DRIP LEG

(SEDIMENT

TRAP)

CAP

GAS SUPPLY PIPING

MANUAL

SHUTOFF

VALVE

GAS

CONTROL

VALVE

GROUND JOINT

UNION

BLACK PIPE

DRIP LEG

(SEDIMENT

TRAP)

CAP

3

″ MIN.

3

″ MIN.

A gas line of sufficient size must be run to the water heater. Consult

the current edition of National Fuel Gas Code ANSI Z223.1, also

referred to as NFPA 54 and the gas company concerning pipe size.

There must be:

— A readily accessible manual shut off valve in the gas supply line

serving the water heater, and

— A drip leg (sediment trap) ahead of the gas control valve to help

prevent dirt and foreign materials from entering the gas control

valve.

— A flexible gas connector or a ground joint union between the

shutoff valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the

water heater. Use a soapy water solution, not a match or open

flame. Rinse off soapy solution and wipe dry.

When installed at elevations above 2,000 feet, input ratings

should be reduced at the rate of 4 percent for each 1,000 feet

above sea level. Installations above 4,000 ft. require replace-

ment of the burner orifice in accordance with the National

Fuel Gas Code ANSI Z223.1 / NFPA 54.

WARNING

The appliance and its individual shutoff valve must be dis-

connected from the gas supply piping system during any pres-

sure testing of that system at test pressures in excess of

1

/

2

pound per square inch (3.5kPa).

The appliance must be isolated from the gas supply piping sys-

tem by closing its individual manual shutoff valve during any

pressure testing of the gas supply piping system at test pres-

sures equal to or less than

1

/

2

pound per square inch (3.5kPa).

WARNING

Failure to replace the orifice could result in improper and

inefficient operation of the appliance, producing carbon

monoxide gas in excess of safe limits, which could result in

serious injury or death. Contact your gas supplier for any

specific changes which may be required in your area.