OREC:
Recooling function
Adjustment: OFF / ON
Recommended setting: ON

The recooling function is used to cool the tank when the
maximum tank temperature (S MX) is exceeded, such as when
the collector cooling function (OCX) is activated and the tank
may reach 190 °F (emergency shut down of the tank).

When the collector is 5° cooler than the tank the pump will run
to dump excess heat from the tank in the piping and at the
solar collector until the tank is cooled to the maximum tank
temperature setting.

The tube collector function is only needed for systems that use
vacuum tube solar collectors.

This function is not necessary for this system.

OTC:
Tube collector function
Adjustment: OFF / ON
Recommended setting: OFF

OHQM:
Heat quantity measurement
Adjustment: OFF / ON
Recommended setting: OFF

A Heat quantity measurement is possible for this system
in conjunction with the fl ow meter. In order for this function
measure the heat gain of the system the optional temperature
sensor 4 (return fl ow sensor) must be added and connected to
the copper pipe between the coil outlet on the tank (marked “to
pump”) and the solar pump station.

FMAX:
Volume fl ow in gal/min
Adjustment range:
0.0 to 20.0 in steps of 0.1
Recommended setting: pump
station fl ow meter reading
converted to (l/min).

For OHQM to give an accurate reading the volume fl ow readable
at the fl owmeter (l/min) must be adjusted in the channel FMAX.

Channel only available when OHQM is active

MEDT:
Type of antifreeze
Adjustment range: 0 to 3
Recommended setting: 1
Channel only available when
OHQM is active.

For OHQM to give an accurate reading the type of heat transfer
fl uid type(antifreeze) must be set in the channel MEDT:
0: water
1: propylene glycol
2: ethylene glycol
3: Tyfocor ® LS / G – LS
Caution: for this system type only type 1: propylene glycol
should be selected. Use of any other type of heat transfer fl uid
in this system may cause damage to the system or present a
health hazard

MED%:
Concentration of antifreeze by
volume %
Adjustment range: 20 to 70%
Recommended setting: 50

The antifreeze concentration by % volume should be entered in
this channel for OHQM to give an accurate reading.

Standard system concentration should be a 50% propylene
glycol and 50% distilled or de-mineralized water.

Channel only available when OHQM is active.

kWh/MWh:
Heat quantity value shown
in the kWh and MWh display
channels. The sum of both
channels form the total heat
output.
Channel only available when
OHQM is active

The total heat quantity value can be reset. When one of the
heat quantity display channels is selected the symbol

is

permanently shown in the display. The set button (3) must be
pressed for approximately 2 seconds in order to go into the
reset mode for the counter. The display symbol

will be

fl ashing and the value for heat quantity will be set to 0. In order
to fi nish the reset procedure the set button (3) must be pressed
in order to confi rm.

In order to interrupt the reset procedure no button should be
pressed for about 5 seconds. The controller will automatically
return to the indication mode with the previous total.