6 module 6 - s, Etpoint, Larm – Red Lion LDSG User Manual

Page 13: Arameters, Parameter menu

Advertising
background image

13

13

6-SPt

ACt-n

Setpoint

Select

SPSEL

Setpoint

Value

SP-n

Setpoint

Assignment

Src-1

Output

Logic

out-n

HYS-n

Setpoint

Hysteresis

tON-n

On Time

Delay

Off Time

Delay

tOF-n

Standby

Operation

Stb-n

Reset

Action

rSt-n

PAR

Pro

Setpoint

Action

LIt-n

Setpoint

Annunciators

6.6 Module 6 - s

etpoInt

(a

larM

) p

araMeters

(



)

PARAMETER MENU

Enter the setpoint (alarm output) to be programmed. The

in the following

parameters will reflect the chosen setpoint number. After the chosen setpoint is

completely programmed, the display will return to

 

. Repeat step for

each setpoint to be programmed. The



chosen at



will return to

 

.

The number of setpoints available is setpoint output card dependent.











SETPOINT SELECT



=

Setpoint always off, (returns to SPSEL NO)



=

Absolute high, with balanced hysteresis



=

Absolute low, with balanced hysteresis



=

Absolute high, with unbalanced hysteresis



=

Absolute low, with unbalanced hysteresis



=

Deviation high, with unbalanced hysteresis *



=

Deviation low, with unbalanced hysteresis *



=

Outside band, with unbalanced hysteresis *



=

Lower Totalizer absolute high, unbalance hysteresis**



=

Upper Totalizer absolute high, unbalance hysteresis**

* Deviation and band action setpoints are relative to the value of setpoint 1.

It is not possible to configure setpoint 1 as deviation or band actions. It is

possible to use setpoint 1 for an absolute action, while its value is being used

for deviation or band.

** The lower Totalizer action



allows setpoints to function off of the

lower 5 digits of the Totalizer. The upper Totalizer action



allows

setpoints to function off of the upper 4 digits of the Totalizer. To obtain

absolute low alarms for the Totalizer, program the



or



output

logic as reverse.

Enter the action for the selected setpoint (alarm output). See Setpoint Alarm

Figures for a visual detail of each action.

SETPOINT ACTION

























Setpoint Alarm Figures

With reverse output logic



, the below alarm states are opposite.

ALARM

STATE

OFF

ON

Hys

SP + Hys

SP

OFF

TRIGGER POINTS

ALARM

STATE

ON

OFF

Hys

SP1 + (-SPn)

SP1

ON

TRIGGER POINTS

Absolute Low Acting (Unbalanced Hys) =



Deviation High Acting (SP

< 0) =



ALARM

STATE

OFF

ON

Hys

SP + ½Hys

SP

SP - ½Hys

OFF

TRIGGER POINTS

ALARM

STATE

OFF

ON

Hys

SP1 + SPn

SP1

OFF

TRIGGER POINTS

ALARM

STATE

ON

OFF

Hys

SP1 - (-SPn)

SP1

ON

TRIGGER POINTS

Absolute Low Acting (Balanced Hys) =



Deviation High Acting (SP

> 0) =



Deviation Low Acting (SP

< 0)=



ALARM

STATE

OFF

ON

Hys

SP

SP - Hys

OFF

TRIGGER POINTS

ALARM

STATE

OFF

ON

Hys

SP1 - SPn

SP1

OFF

TRIGGER POINTS

ALARM

STATE

OFF

ON

Hys

SP1 - SPn

SP1

OFF

SP1 + SPn

ON

OFF

Hys

TRIGGER POINTS

Absolute High Acting (Unbalanced Hys) =



This is also for Totalizer alarms:



, 

Deviation Low Acting (SP > 0) =



Band Outside Acting =



ALARM

STATE

OFF

ON

Hys

SP + ½Hys

SP

SP - ½Hys

OFF

TRIGGER POINTS

Absolute High Acting (Balanced Hys) =



For maximum input frequency, unused Setpoints should be configured for



action. The setpoint assignment and the setpoint action determine certain

setpoint feature availability.

Advertising