Max./Min. capture delay time: 0 to 3275 sec.

9. USER INPUTS: Three programmable user inputs

Max. Continuous Input: 30 VDC

Isolation To Sensor Input Common: Not isolated.

Response Time: 50 msec. max.

Logic State: Jumper selectable for sink/source logic

INPUT STATE

SINKING INPUTS

22 K pull-up to +5 V

SOURCING INPUTS

22 K pull-down

Active

V

IN

< 0.9 VDC

V

IN

> 3.6 VDC

Inactive

V

IN

> 3.6 VDC

V

IN

< 0.9 VDC

10. TOTALIZER:

Function:

Time Base: second, minute, hour, or day

Batch: Can accumulate (gate) input display from a user input

Time Accuracy: 0.01% typical

Decimal Point: 0 to 0.0000

Scale Factor: 0.001 to 65.000

Low Signal Cut-out: -19,999 to 99,999

Total: 9 digits, display alternates between high order and low order readouts

11. DISPLAY MESSAGES:

“OLOL” - Appears when measurement exceeds + signal range.

“ULUL” - Appears when measurement exceeds - signal range

“. . . .” - Appears when display values exceed + display range.

“- . . .” - Appears when display values exceed - display range.

“E . . .” - Appears when Totalizer exceeds 9 digits.

“h . . .” - Denotes the high order display of the Totalizer.

12. COMMUNICATIONS:

Type: RS485 or RS232

Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.

Working Voltage: 50 V. Not Isolated from all other commons.

Data: 7/8 bits

Parity: no, odd or even

Baud Rate: 300 to 38.4 K

Bus Address: Selectable 0 to 99, Max. 32 meters per line (RS485)

13. MEMORY: Nonvolatile E

2

PROM retains all programming parameters and

max/min values when power is removed.

14. OUTPUT:

Type: Dual FORM-C relay

Isolation To Sensor & User Input Commons: 1400 Vrms for 1 min.

Working Voltage: 150 Vrms

Contact Rating: 5 amps @ 120/240 VAC or 28 VDC (resistive load), 1/8

H.P. @ 120 VAC (inductive load)

Life Expectancy: 100,000 minimum operations

Response Time:

Turn On Time: 4 msec max.

Turn Off Time: 4 msec max.

15. ENVIRONMENTAL CONDITIONS:

Operating temperature: 0 to 65 °C

Storage temperature: -40 to 70 °C

Operating and storage humidity: 0 to 85% max. RH (non-condensing)

Vibration to IEC 68-2-6: Operational 5-150 Hz, 2 g (1g relay)

Shock to IEC 68-2-27: Operational 30 g (10 g relay)

Altitude: Up to 2,000 meters

16. CONNECTIONS:Internal removable terminal blocks

Wire Strip Length: 0.4" (10 mm)

Wire Gage: 24-12 AWG copper wire, 90°C rated insulation only

Torque: 5.3 inch-lbs (0.6 N-m) max.

Cable Diameter: Outside diameter must be 0.181" (4.6 mm) to 0.312" (7.9

mm) to maintain Type 4 rating of cord grips.

17. CONSTRUCTION: Aluminum enclosure, and steel side panels with textured

black polyurethane paint for scratch and corrosion resistance protection. Meets

Type 4X/IP65 specifications. Installation Category II, Pollution Degree 2.

18. CERTIFICATIONS AND COMPLIANCES:

CE Approved:

EN 61326-1 Immunity to Industrial Locations

Emission CISPR 11 Class A

Safety requirements for electrical equipment for measurement control, and

laboratory use:

EN 61010-1: General Requirements

EN 61010-2-030: Particular Requirements for Testing and Measuring

Circuits

Type 4X Enclosure rating (Face only)

IP65 Enclosure rating (Face only)

Refer to EMC Installation Guidelines section of the bulletin for additional

information.

19. WEIGHT:

LD2 - 4.5 lbs (2.04 kg)

LD4 - 10.5 lbs (4.76 kg)

1.0 I

nstallIng

the

M

eter

INPUT RANGE JUMPER

The jumpers to select input range, excitation, voltage and user input

configuration must be selected before wiring the meter. The jumpers

for the LD2 model are located on the left side of the unit, and the

jumpers for the LD4 model are located on the right side of the unit.

Warning: Exposed line voltage exists on the circuit

boards. Remove all power to the meter and load circuits

before accessing inside of the meter.

2.0 s

ettIng

the

J

uMpers

-IN

+EXC

4

3

2

1

TBC

-EXC

+IN

RANGE SELECT

JUMPERS

5V

10V

EXCITATION

INPUT

USER 2

3

USER COMM

1

2

USER 1

TBD

USER 3

SRC

SNK

4

USER

RANGE

200mV

20mV

INSTALLATION

The meter meets Type 4X/IP65 requirements when properly installed.

LDPLUG00 plugs should be installed in open water-tight connectors.

INSTALLATION ENVIRONMENT

The unit should be installed in a location that does not exceed the operating

temperature. Placing the unit near devices that generate excessive heat should

be avoided. The unit should only be cleaned with a soft cloth and neutral soap

product. Do NOT use solvents.

Continuous exposure to direct sunlight may accelerate the aging process of

the front overlay. Do not use tools of any kind (screwdrivers, pens, pencils, etc.)

to operate the keypad of the unit.

MOUNTING INSTRUCTIONS

This display is designed to be

wall mounted or suspended

from a ceiling truss or other

suitable structure capable of

supporting the LDSG.

Caution should be exercised

when hanging the display to

provide for the safety of

personnel. If hanging the LDSG,

run the suspension cables (or

chains) through the mounting

bracket holes. For wall mounting

use #10-32 size bolts.

MOUNTING HOLE (.281")

MUST BE

CONNECTED TO

TERMINAL #3 (TBA)

EXCITATION

RANGE

RANGE SELECT

2

USER 1

USER 2

USER 3

+EXC

-EXC

200mV

JUMPERS

20mV

2

+IN

3

4

-IN

1

5V

10V

3

4

TBC

TBD

USER COMM

INPUT

USER

SNK

SRC

1

LD2 JUMPERS

LD4 JUMPERS