1 module 1 - s, Ignal, Nput – Red Lion LDSG User Manual

Page 6: Arameters

Advertising
background image

66

ALTERNATING SELECTION DISPLAY

In the module description sections which follow, the dual display with arrows

appears for each programming parameter. This is used to illustrate the display

alternating between the parameter (top display) and the parameter's Factory

Setting (bottom display). In most cases, selections or value ranges for the

parameter will be listed on the right.

STEP BY STEP PROGRAMMING INSTRUCTIONS:

PROGRAMMING MODE ENTRY (PAR KEY)

The Programming Mode is entered by pressing the

PAR

key. If this mode is

not accessible, then meter programming is locked by either a security code or a

hardware lock. (See Modules 2 and 3 for programming lock-out details.)

MODULE ENTRY (ARROW & PAR KEYS)

Upon entering the Programming Mode, the display alternates between 

and the present module (initially ). The arrow keys (

F1

and

F2

) are used

to select the desired module, which is then entered by pressing the

PAR

key.

PARAMETER (MODULE) MENU (PAR KEY)

Each module has a separate parameter menu. These menus are shown at the

start of each module description section which follows. The

PAR

key is pressed

to advance to a particular parameter to be changed, without changing the

programming of preceding parameters. After completing a module, the display

will return to  . From this point, programming may continue by selecting

and entering additional modules. (See

MODULE ENTRY above.)

PARAMETER SELECTION ENTRY (ARROW & PAR KEYS)

For each parameter, the display alternates between the parameter and the

present selection or value for that parameter. For parameters which have a list

of selections, the arrow keys (

F1

and

F2

) are used to sequence through the

list until the desired selection is displayed. Pressing the

PAR

key stores and

activates the displayed selection, and also advances the meter to the next

parameter.

NUMERICAL VALUE ENTRY (ARROW, RST & PAR KEYS)

For parameters which require a numerical value entry, the arrow keys can be

used to increment or decrement the display to the desired value. When an arrow

key is pressed and held, the display automatically scrolls up or scrolls down.

The longer the key is held, the faster the display scrolls.

The

RST

key can be used in combination with the arrow keys to enter large

numerical values. When the

RST

key is pressed along with an arrow key, the

display scrolls by 1000’s. Pressing the

PAR

key stores and activates the

displayed value, and also advances the meter to the next parameter.

PROGRAMMING MODE EXIT (DSP KEY or PAR KEY at

 

)

The Programming Mode is exited by pressing the

DSP

key (from anywhere

in the Programming Mode) or the

PAR

key (with   displayed). This will

commit any stored parameter changes to memory and return the meter to the

Display Mode. If a parameter was just changed, the

PAR

key should be pressed

to store the change before pressing the

DSP

key. (If power loss occurs before

returning to the Display Mode, verify recent parameter changes.)

5.1 Module 1 - s

Ignal

I

nput

p

araMeters

(



)

1-INP

Display

Decimal Point

dECPt

Input

Range

rAN6E

Display

Rounding

round

Scaling

Style

StYLE

FILtr

Filter

Setting

bANd

Filter

Band

Scaling

Points

PtS

Display x

Value

dSP

Input x

Value

INP

x

x

PAR

Pro

PARAMETER MENU





INPUT RANGE

Select the input range that corresponds to the external signal. This selection

should be high enough to avoid input signal overload but low enough for the

desired input resolution. This selection and the position of the Input Range

Jumper must match.

RANGE

RESOLUTION



SELECTION

±24 mV



±240 mV











DISPLAY DECIMAL POINT

Select the decimal point location for the Input,

MAX and MIN displays. (The

TOT display decimal point is a separate parameter.) This selection also affects



,



and



parameters and setpoint values.



DISPLAY ROUNDING*









Rounding selections other than one, cause the Input Display to ‘round’ to the

nearest rounding increment selected (ie. rounding of ‘5’ causes 122 to round to

120 and 123 to round to 125). Rounding starts at the least significant digit of

the Input Display. Remaining parameter entries (scaling point values, setpoint

values, etc.) are not automatically adjusted to this display rounding selection.





FILTER SETTING*

The input filter setting is a time constant expressed in tenths of a second. The

filter settles to 99% of the final display value within approximately 3 time

constants. This is an Adaptive Digital Filter which is designed to steady the

Input Display reading. A value of ‘0’ disables filtering.



to



seconds

Indicates Program Mode Alternating Display

Parameter

Selection/Value





Advertising