13

RESET MINIMUM





When activated (momentary action),



flashes and the Minimum reading

is set to the present assigned value. The Minimum function then continues from

that value. This selection functions independent of the selected display.













RESET MAXIMUM AND MINIMUM

When activated (momentary action),



flashes and the Maximum and

Minimum readings are set to the present assigned values. The Maximum and

Minimum function then continues from that value. This selection functions

independent of the selected display.

Note: Following display functions are only available on User Input.





ADVANCE DISPLAY

When activated (momentary action), the display advances to the next display

that is not locked out from the Display Mode.





SELECT DISPLAY A

When activated (momentary action), the display advances to Display A,

if enabled.





SELECT DISPLAY B

When activated (momentary action), the display advances to Display B,

if enabled.





SELECT DISPLAY C

When activated (momentary action), the display advances to Display C,

if enabled.





SELECT DISPLAY _

When activated (momentary action), the display advances to the Display _

(no annunciator), if enabled.









CHANGE DISPLAY INTENSITY LEVEL

When activated (momentary action), the display intensity changes to the next

intensity level (of 4). The four levels correspond to Display Intensity Level

(



) settings of 0, 3, 8, and 15.

SETPOINT SELECTIONS



-

Select main or alternate setpoints



-

Reset Setpoint 1 (Alarm 1)



-

Reset Setpoint 2 (Alarm 2)



-

Reset Setpoint 3 (Alarm 3)



-

Reset Setpoint 4 (Alarm 4)



-

Reset Setpoint 3 & 4 (Alarm 3 & 4)



-

Reset Setpoint 2, 3 & 4 (Alarm 2, 3 & 4)



-

Reset Setpoint All (Alarm All)

The following selections are functional only with the Setpoint plug-in card

installed. Refer to Module 6 - Setpoint (Alarm) Parameters for an explanation of

their operation.

м

н

о

Setpoint

Card

Only









SELECT SETPOINT LIST

Two lists of values are available for



,



,



,



. The two lists are

named



and



. If a user input is used to select the list then



is

selected when the user input is not active and and



is selected when the

user input is active (maintained action). If a front panel key is used to select the

list then the list will toggle for each key press (momentary action). The display

will only indicate which list is active when the list is changed.

To program the values for



and



, first complete the programming

of all the parameters. Exit programming and switch to the other list. Re-enter

programming and enter the values for



,



,



,



. If any other

parameters are changed then the other list values must be reprogrammed.









PRINT REQUEST

The meter issues a block print through the serial port when activated, and the

serial type is set to



. The data transmitted during a print request and the serial

type is programmed in Module 7. If the user input is still active after the

transmission is complete (about 100 msec), an additional transmission occurs.

As long as the user input is held active, continuous transmissions occur.