8 module 8 - a, Out asin, Type an-lo an-hi udt – Red Lion PAXDP User Manual

Page 26: Nalog, Utput, Arameters

Advertising
background image

26

26

8-Out

ASIN

Analog

Type

tYPE

AN-LO

AN-HI

udt

Analog

Update Time

PAR

Analog

Assignment

Analog Low

Scale Value

Analog High

Scale Value

Pro

6.8 mOdule 8 - a

nalOg

O

uTpuT

p

arameTers

(



) Ñ

PARAMETER MENU

Enter the analog output type. For 0-20 mA or 4-20 mA

use terminals 18 and 19. For 0-10 V use terminals 16 and

17. Only one range can be used at a time.









ANALOG TYPE

ANALOG ASSIGNMENT

Enter the Display Value that corresponds to 0 mA (0-20

mA) , 4 mA (4-20 mA) or 0 VDC (0-10 VDC).





ANALOG LOW SCALE VALUE









ANALOG HIGH SCALE VALUE

ANALOG UPDATE TIME



to





to





to



Enter the source for the analog output to retransmit:



= Relative (net) Input Value. The Relative Input

Value is the Absolute Input Value that includes

the Display Offset Value.



= Absolute (gross) Input Value. The Absolute Input

Value is based on Module 1



and



entries.



= Calculation Value



= Totalizer Value



= Minimum Display Value



= Maximum Display Value

Enter the Display Value that corresponds to 20 mA (0-20

mA) , 20 mA (4-20 mA) or 10 VDC (0-10 VDC).

Enter the analog output update rate in seconds. A value

of 0.0 allows the meter to update the analog output at the

ADC Conversion Rate.

RANGE

0 to 20 mA
4 to 20 mA

0 to 10 V

SELECTION























Ñ

- An analog output card must be installed in order to access this

module.

Advertising