Eneral, Eter, Pecifications – Red Lion PAXDP User Manual

Page 3

Advertising
background image

3

g

eneral

m

eTer

s

peCifiCaTiOns

1. DISPLAY: 5 digit, 0.56" (14.2 mm) variable intensity red sunlight readable

(-19999 to 99999)

2. POWER:

AC Versions:

AC Power: 85 to 250 VAC, 50/60 Hz, 21 VA

Isolation: 2300 Vrms for 1 min. to all inputs and outputs.

DC Versions: (Derate operating temperature to 40° C if three plug-in option

cards or PAXCDC50 are installed.)

DC Power: 18 to 36 VDC, 13 W

AC Power: 24 VAC, ± 10%, 50/60 Hz, 16 VA

Isolation: 500 Vrms for 1 min. to all inputs and outputs (50 V working).

Must use a Class 2 or SELV rated power supply

3. ANNUNCIATORS:

A - Programmable Display

B - Programmable Display

C - Programmable Display

SP1 - Setpoint alarm 1 is active

SP2 - Setpoint alarm 2 is active

SP3 - Setpoint alarm 3 is active

SP4 - Setpoint alarm 4 is active

Units Label - Optional units label backlight

4. KEYPAD: 3 programmable function keys, 5 keys total

5. A/D CONVERTER: 16 bit resolution

6. UPDATE RATES:

A/D conversion rate: Adjustable 5.3 to 105 readings/sec.

Step response: (to within 99% of final readout value with digital filter disabled)

Display update rate: adjustable 1 to 20 readings/sec.

Setpoint output on/off delay time: 0 to 3275 sec.

Analog output update rate: 0 to 10 sec

Max./Min. capture delay time: 0 to 3275 sec.

7. DISPLAY MESSAGES:

“OLOL” - Appears when measurement exceeds + signal range.

“ULUL” - Appears when measurement exceeds - signal range

“. . . .” - Appears when display values exceed + display range.

“- . . .” - Appears when display values exceed - display range.

8. SENSOR INPUTS:

* After 20 minute warm-up. Accuracy is specified in two ways: Accuracy over

an 18 to 28°C and 10 to 75% RH environment; and accuracy over a 0 to 50°C

and 0 to 85% RH (non-condensing environment). Accuracy over the 0 to

50°C range includes the temperature coefficient effect of the meter.

9. EXCITATION POWER:

Transmitter Power: 18 VDC, ±20%, unregulated, 70 mA max. per

input channel.

10. LOW FREQUENCY NOISE REJECTION:

Normal Mode: (digital filter off)

*Note: 19.8 Hz Input Rate provides best rate performance and simultaneous

50/60 Hz rejection.

Common Mode: >100 dB @ 50/60 ±1 Hz (19.8 or 20 Input Rate)

11. USER INPUTS: Three programmable user inputs

Max. Continuous Input: 30 VDC

Isolation To Sensor Input A Common: 500 Vrms for 1 min;

Working Voltage: 50 V

Isolation To Sensor Input B Common: Not isolated.

Response Time: 20 msec. max.

Logic State: Jumper selectable for sink/source logic

12. TOTALIZER:

Function:

Time Base: second, minute, hour, or day

Batch: Can accumulate (gate) input display from a user input

Time Accuracy: 0.01% typical

Decimal Point: 0 to 0.0000

Scale Factor: 0.001 to 65.000

Low Signal Cut-out: -19,999 to 99,999

Total: 9 digits, display alternates between high order and low order readouts

13. CUSTOM LINEARIZATION:

Data Point Pairs: Selectable from 2 to 16

Display Range: -19,999 to 99,999

Decimal Point: 0 to 0.0000

14. MEMORY: Nonvolatile memory retains all programmable parameters and

display values.

15. CERTIFICATIONS AND COMPLIANCES:

CE Approved

EN 61326-1 Immunity to Industrial Locations

Emission EN 55011 Class A

IEC/EN 61010-1

UL Recognized Component: File #E179259

UL Listed: File #E137808

Type 4X Enclosure rating (Face only)

IP65 Enclosure rating (Face only)

IP20 Enclosure rating (Rear of unit)

Refer to EMC Installation Guidelines section of the bulletin for additional

information.

16. ENVIRONMENTAL CONDITIONS:

Operating Temperature Range: 0 to 50°C (0 to 45°C with all three plug-in

option cards installed)

Storage Temperature Range: -40 to 60°C

Vibration to IEC 68-2-6: Operational 5-150 Hz, 2 g

Shock to IEC 68-2-27: Operational 25 g (10 g relay)

Operating and Storage Humidity: 0 to 85% max. RH non-condensing

Altitude: Up to 2000 meters

17. CONNECTIONS: High compression cage-clamp terminal block

Wire Strip Length: 0.3" (7.5 mm)

Wire Gage: 30-14 AWG copper wire

Torque: 4.5 inch-lbs (0.51 N-m) max.

18. CONSTRUCTION: This unit is rated for NEMA 4X/IP65 outdoor use.

IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece

bezel/case. Flame resistant. Synthetic rubber keypad. Panel gasket and

mounting clip included.

19. WEIGHT: 10.4 oz. (295 g)

V

IN

> 3.6 VDC

V

IN

< 0.9 VDC

Inactive

V

IN

< 0.9 VDC

V

IN

> 3.6 VDC

Active

SINKING INPUTS

22 K pull-up to +5 V

SOURCING INPUTS

22 K pull-down

INPUT STATE

INPUT

(RANGE)

ACCURACY*

(18 to 28°C)

ACCURACY*

(0 to 50°C)

IMPEDANCE/

COMPLIANCE

MAX

CONTINUOUS

OVERLOAD

DISPLAY

RESOLUTION

±20 mA

(-26 to

26 mA)

0.03% of

reading +2 µA

0.12% of

reading +3 µA 24.6 ohm

90 mA

1 µA

±10 VDC

(-13 to

13 VDC)

0.03% of

reading +2 mV

0.12% of

reading +3 mV 500 Kohm

50 V

1 mV

INPUT UPDATE RATE

MAX. TIME (msec)

5.3

770

7.5

560

16.7

260

19.8

220

20

220

30

150

105

60

INPUT UPDATE RATE

50 Hz ±1 Hz

60 Hz ±1 Hz

5.3

>90 dB

>65 dB

7.5

>60 dB

>55 dB

16.7

>100 dB

>50 dB

19.8*

>60 dB

>95 dB

20

>55 dB

>100 dB

30

>20 dB

>20 dB

105

>20 dB

>13 dB

Advertising