Ptional, Utput, Ards – Red Lion PAXDP User Manual

Page 4: Ccessories, Adding option cards, Communication cards (paxcdc), Setpoint cards (paxcds)

Advertising
background image

WARNING: Disconnect all power to the unit before

installing Plug-in cards.

Adding Option Cards

The PAX and MPAX series meters can be fitted with up to three optional plug-

in cards. The details for each plug-in card can be reviewed in the specification

section below. Only one card from each function type can be installed at one time.

The function types include Setpoint Alarms (PAXCDS), Communications

(PAXCDC), and Analog Output (PAXCDL). The plug-in cards can be installed

initially or at a later date.

COMMUNICATION CARDS (PAXCDC)

A variety of communication protocols are available for the PAX and MPAX

series. Only one of these cards can be installed at a time. Note: For Modbus

communications use RS485 Communications Output Card and configure

communication () parameter for Modbus.

PAXCDC10 - RS485 Serial (Terminal)

PAXCDC30 - DeviceNet

PAXCDC1C - RS485 Serial (Connector)

PAXCDC50 - Profibus-DP

PAXCDC20 - RS232 Serial (Terminal)

PAXUSB00 - USB (Mini B)

PAXCDC2C - RS232 Serial (Connector)

SERIAL COMMUNICATIONS CARD

Type: RS485 or RS232

Communication Type: RLC Protocol (ASCII), Modbus RTU, and Modbus

ASCII

Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.

Working Voltage: 50 V. Not Isolated from all other commons.

Baud: 300 to 38,400

Data: 7/8 bits

Parity: No, Odd or Even

Bus Address: Selectable 0 to 99 (RLC Protocol), or 1 to 247 (Modbus

Protocol), Max. 32 meters per line (RS485)

Transmit Delay: Selectable for 0 to 0.250 sec (+2 msec min)

DEVICENET™ CARD

Compatibility: Group 2 Server Only, not UCMM capable

Baud Rates: 125 Kbaud, 250 Kbaud, and 500 Kbaud

Bus Interface: Phillips 82C250 or equivalent with MIS wiring protection per

DeviceNet™ Volume I Section 10.2.2.

Node Isolation: Bus powered, isolated node

Host Isolation: 500 Vrms for 1 minute (50 V working) between DeviceNet™

and meter input common.

PROFIBUS-DP CARD

Fieldbus Type: Profibus-DP as per EN 50170, implemented with Siemens

SPC3 ASIC

Conformance: PNO Certified Profibus-DP Slave Device

Baud Rates: Automatic baud rate detection in the range 9.6 Kbaud to 12 Mbaud

Station Address: 0 to 125, set by rotary switches.

Connection: 9-pin Female D-Sub connector

Network Isolation: 500 Vrms for 1 minute (50 V working) between Profibus

network and sensor and user input commons. Not isolated from all other

commons.

PAXUSB PROGRAMMING CARD

Type: USB Virtual Comms Port

Connection: Type mini B

Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.

Working Voltage: 50 V. Not Isolated from all other commons.

Baud Rate: 300 to 19.2k

Unit Address: 0 to 99; only 1 meter can be configured at a time

SETPOINT CARDS (PAXCDS)

The PAX and MPAX series has 4 available setpoint alarm output plug-in

cards. Only one of these cards can be installed at a time. (Logic state of the

outputs can be reversed in the programming.) These plug-in cards include:

PAXCDS10 - Dual Relay, FORM-C, Normally open & closed

PAXCDS20 - Quad Relay, FORM-A, Normally open only

PAXCDS30 - Isolated quad sinking NPN open collector

PAXCDS40 - Isolated quad sourcing PNP open collector

DUAL RELAY CARD

Type: Two FORM-C relays

Isolation To Sensor & User Input Commons: 2000 Vrms for 1 min.

Working Voltage: 240 Vrms

Contact Rating:

One Relay Energized: 5 amps @ 120/240 VAC or 28 VDC (resistive load),

1/8 HP @120 VAC, inductive load

Total current with both relays energized not to exceed 5 amps

Life Expectancy: 100 K cycles min. at full load rating. External RC snubber

extends relay life for operation with inductive loads

QUAD RELAY CARD

Type: Four FORM-A relays

Isolation To Sensor & User Input Commons: 2300 Vrms for 1 min.

Working Voltage: 250 Vrms

Contact Rating:

One Relay Energized: 3 amps @ 240 VAC or 30 VDC (resistive load), 1/10

HP @120 VAC, inductive load

Total current with all four relays energized not to exceed 4 amps

Life Expectancy: 100 K cycles min. at full load rating. External RC snubber

extends relay life for operation with inductive loads

QUAD SINKING OPEN COLLECTOR CARD

Type: Four isolated sinking NPN transistors.

Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.

Working Voltage: 50 V. Not Isolated from all other commons.

Rating: 100 mA max @ V

SAT

= 0.7 V max. V

MAX

= 30 V

QUAD SOURCING OPEN COLLECTOR CARD

Type: Four isolated sourcing PNP transistors.

Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.

Working Voltage: 50 V. Not Isolated from all other commons.

Rating: Internal supply: 24 VDC ± 10%, 30 mA max. total

External supply: 30 VDC max., 100 mA max. each output

ALL FOUR SETPOINT CARDS

Response Time: See update rates step response specification; add 6 msec

(typical)for relay card

O

pTiOnal

p

lug

-

in

O

uTpuT

C

ards

4

a

CCessOries

UNITS LABEL KIT (PAXLBK)

Each meter has a units indicator with backlighting that can be customized

using the Units Label Kit. The backlight is controlled in the programming.

PROGRAMMING SOFTWARE

The Crimson

®

2 (SFCRM2) software is a Windows

®

based program for

configuring and updating the firmware of the PAXDP meter from a PC. Using

the software makes programming the PAXDP meter easier and allows the user

to save the PAXDP database in a PC file for future use. The software is available

as a free download from Red Lion’s website.

The first time Crimson 2 software is run from the File menu, select “New” to

display a dialog and select the PAXDP. The screen will display icons that

represent the various programming sections of the PAXDP. Double-click on an

icon to configure the programming parameters pertaining to the selection. Tool

Tip help is available for each of the program parameters. A PAX serial plug-in

card or PAX USB programming card is required to program the meter using the

software.

When communicating with Crimson 2 software, the PAXDP must be set in

default configuration type of:

Communications Type: MODBUS RTU

Baud Rate: 38400

Data Bit: 8

ParityBit: no

Meter Unit Address: 247