User inputs, Program disable plug jumper, Output wiring – Red Lion C48T User Manual

Page 14

Advertising
background image

-8-

User Inputs

The three external user inputs are programmable inputs that can be

configured as current sinking (active low) or current sourcing (active high)
inputs via a single plug jumper. Programmable external user inputs are digital
inputs. The use of shielded cable is recommended. Follow the EMC Installation
Guidelines for shield connection. See User Inputs, page 19, for a description of
all available user input functions. The active logic state of ALL user inputs is
dictated by the position of the User Input plug jumper. The plug jumper is
located on the CPU board (See Figure 9, User Input and Program Disable
Jumper Locations).

OUTPUT WIRING

Relay Connections

To prolong contact life and suppress electrical noise interference due to the

switching of inductive loads, it is good installation practice to install a snubber
across the contactor. Follow the manufacturer’s instructions for installation.
Note: Snubber leakage current can cause some electro-mechanical devices to be

held ON.

Program Disable Plug Jumper

The program disable plug jumper is used to enable and disable front panel

programming of the C48T. See Front Panel Accessible Functions With Program
Disable, page 11, for a description of available functions. The plug jumper is
located on the CPU board (See Figure 9, User Input and Program Disable
Jumper Locations).

Figure 9, User Input and Program Disable Jumper Locations

Figure 7, User Input Jumper Settings

Figure 8, Program Disable Jumper Settings

User Input State

Input Voltage Level for Jumper Position

Source

Sink *

Active

Vin > 3.5 VDC

Vin < 1.5VDC

Inactive

Vin < 1.5 VDC

Vin > 3.5VDC

* Factory Setting

C48t-im.QXD 3/5/04 3:28 PM Page 8