“DC Out/In” and “Comm.” terminals. This supply will determine the
PNP output voltage level, and must be in the range of +13 to +30 VDC.

An external supply can provide the additional output sourcing current

required in applications where two or more outputs are “ON”
simultaneously. However, the maximum rating of 100 mA per individual
output must not be exceeded, regardless of external supply capacity.

Relay: Form A contact, Rating = 5 A @ 250 VAC, 30 VDC (resistive load),

1/10 HP @ 120 VAC (inductive load)
Relay Life Expectancy: 100,000 cycles min. at max. load rating

Programmable Timed Output(s) User selectable output time resolution:

0.01 Second Resolution: 0.01 to 99.99 seconds, ± 0.01% + 10 msec max.
0.1 Second Resolution: 0.1 to 999.9 Seconds, ± 0.01% + 100 msec max.

8. RS485 SERIAL COMMUNICATIONS (Optional): Up to 32 units can be

connected.
Baud Rate: Programmable from 1200 to 9600 baud
Address: Programmable from 0 to 99
Data Format: 10 Bit Frame, 1 start bit, 7 or 8 data bits, 1 or No Parity bit,

and 1 stop bit

Parity: Programmable for Odd (7 data bits), Even (7 data bits), or None (8

data bits)

9. ELECTRICAL CONNECTION: Wire clamping screw terminals.
10. ENVIRONMENTAL CONDITIONS:

Operating Temperature: 0 to 50°C
Storage Temperature: -40 to 70°C
Operating and Storage Humidity:

85% max. relative humidity (non-condensing) from 0°C to 50°C.

Altitude: Up to 2000 meters

11. CONSTRUCTION: Black plastic case with collar style panel latch. The

panel latch can be installed for horizontal or vertical stacking. Black plastic
textured bezel with clear display viewing window. Unit assembly with circuit
boards can be removed from the case without removing the case from the
panel or disconnecting the wiring. This unit is rated for NEMA 4X/IP65
indoor use. Installation Category II, Pollution Degree 2.

12. CERTIFICATIONS AND COMPLIANCES:

SAFETY
UL Recognized Component, File #E137808, UL508, CSA 22.2 No. 14

Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.

Type 4X Indoor Enclosure rating (Face only), UL50

IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment for

measurement, control, and laboratory use, Part 1.

IP65 Enclosure rating (Face only), IEC 529

ELECTROMAGNETIC COMPATIBILITY

Notes:
AC VERSIONS
1. A power line filter, RLC#LFIL0000 or equivalent, was installed when the

unit was DC powered.

DC VERSIONS

To insure compliance with the EMC standards listed above, do not connect
any wires from the terminal(s) labeled “COMM.” to the “DC-” supply
terminal (12), when powering the unit from a DC supply.

Refer to EMC Installation Guidelines section of the manual for additional

information.

13. WEIGHT: 6.0 oz (170 g)

-32-

Enclosure class A

EN 55011

RF interference

Emissions to EN 50081-2

Level 3; 10 V/m

ENV 50204

Simulation of cordless telephone

150 KHz - 80 MHz

Level 3; 10 V/rms

EN 61000-4-6

RF conducted interference

Level 3; 2 Kv power

Level 4; 2 Kv I/O

EN 61000-4-4

Fast transients (burst)

80 MHz - 1 GHz

Level 3; 10 V/m

EN 61000-4-3

Electromagnetic RF fields

Level 3; 8 Kv air

Level 2; 4 Kv contact

EN 61000-4-2

Electrostatic discharge

200 Hz, 50% duty cycle

Immunity to EN 50082-2

900 MHz ± 5 MHz

C48t-im.QXD 3/5/04 3:29 PM Page 32