Environmental specifications, Electrical specifications, Mechanical specifications – Notifier FSB-200(A)/-200S(A) User Manual

Page 2: Sensitivity selection

Advertising
background image

Page 2 of 4 — DN-6985:C • 11/16/09

Test/reset features:
• Integral sensitivity test filter (FSB-200S only, requires

external power supply).

• Sensitivity filter (incremental scale on reflector).
• Local alarm test switch.
• Local alarm reset switch.
• Remote test and reset switch (compatible with RTS151 and

RTS151KEY test stations).

Smoke Detector Spacing: On smooth ceilings, 30 – 60 feet

(9.1 to 18.3 m) between projected beams and not more than

one-half that spacing between a projected beam and a

sidewall. Other spacing may be used depending on ceiling

height, airflow characteristics, and response requirements.

See NFPA 72.

ENVIRONMENTAL SPECIFICATIONS

Temperature: –22°F to 131°F (–30°C to 55°C).
Humidity: 10 – 93% RH noncondensing.

ELECTRICAL SPECIFICATIONS

Voltage: 15 to 32 VDC.

Average Standby Current (24 VDC): 2 mA maximum

(LED flashing, SLC @ 24 V).

Alarm Current (LED on): 8.5 mA maximum.

Trouble Current (LED on): 4.5 mA maximum.

Alignment Current: 20 mA maximum.

External Supply (FSB-200S only):

Voltage — 15 to 32 VDC

Current — 0.5 A maximum.

Remote Output (Alarm):

Voltage

- 15 to 32 VDC (Output voltage same as device

input voltage)

Current

- 15 mA maximum, 6 mA minimum (Output current

is limited by 2.2K ohm resistor)

Heater Kit BEAMHK:

Voltage

- 15 to 32 V;

Current

- 92 mA

maximum @ 32 V (heater only);

Power Consumption

-

nominal 1.6 W @ 24 V, maximum 3.0 W @ 32 V.

Reflector Heater Kit BEAMHKR:

Voltage

- 15 to 32 V;

Current

- 450 mA maximum @ 32 V (per reflector);

Power

Consumption (per reflector)

- nominal 7.7 W @ 24 V,

maximum 15.0 W @ 32 V.

MECHANICAL SPECIFICATIONS

Shipping Weight: 3.7 lbs (1.68 kg)
Detector Dimensions: 10.0" H x 7.5" W x 3.3" D (254 mm H x

191 mm W x 84 mm D).
Reflector Dimensions for 16' to 230' (5 to 70m)

Applications: 7.9" x 9.1" (200 x 230 mm).
Reflector Dimensions for Applications Beyond 230'/70m:

15.7" x 18.1" (400 x 460 mm).

SENSITIVITY SELECTION

The detector has six sensitivity selections (sensitivity settings

are a feature of specific control panels). Each of these

selections is only acceptable over a specific distance

separation between the detector and the reflector per UL 268.

The chart below determines which selections are acceptable

for your installed distance. The sensitivity of the detector can

be set only when the housing is removed and the detector is

not in the fine adjustment step of the alignment mode,

indicated by the illumination of the dual digital display. To set

the sensitivity, depress the sensitivity button one time. See

Switch Locations diagram. Once the switch is pressed, the

digital display will illuminate and read the current sensitivity

setting in percent obscuration. To change the sensitivity,

continue to depress the sensitivity switch until the desired

setting is achieved. The digital display will turn off

automatically if no further switch presses occur.

In addition to the four standard sensitivity selections, the

detector has two Acclimate® settings. When either Acclimate®

setting is chosen the detector will automatically adjust its

sensitivity using advanced software algorithms to select the

optimum sensitivity for the environment. The sensitivity will be

continuously adjusted within the ranges specified in the chart

above.

Total obscuration

can be converted to percent per foot,

assuming uniform smoke density for the entire length of the

beam. The chart below converts total obscuration percent per

foot for all acceptable sensitivity settings.

Sensitivity

Setting

Percent

Obscuration

Display

Reading

Acceptable

DISTANCE

between

Detector

and

Reflector

(ft)

Acceptable

DISTANCE

between

Detector

and

Reflector

(m)

Level 1

25%

25

16.4 to 120 5.0 to 36.6

Level 2

30%

30

25 to 150

7.6 to 45.7

Level 3

40%

40

60 to 220

18.3 to 67

Level 4

50%

50

80 to 328

24.4 to 100

Acclimate ®

Level 1

30% to 50%

A1

80 to 150 24.4 to 45.7

Acclimate ®

Level 2

40% to 50%

A2

80 to 200

24.4 to 67

Advertising