Specifications, Product line information – Notifier ND-100R User Manual

Page 2

Advertising
background image

Page 2 of 4 — DN-7006 • 05/09/05

SPECIFICATIONS

ND-100

Operating voltage range: 15 to 30 VDC.

Standby current: 300 µA @ 24 VDC (one communication
every 5 seconds with LED blink enabled).

Operating temperature range: 32° to 131°F (0° to 55°C).

Operating humidity range: 10% to 93% relative humidity (non-
condensing).

Storage temperature range: –22°F to +158°F (–30°C to
+70°C).

Duct air velocity: 100 to 4,000 feet/min (0.5 to 20.32 m/s).

Shipping weight: 3.35 lbs. (1.5 kg).

Dimensions: 14.75" (37 cm) length x 5.50" (14 cm) width x
2.75" (7 cm) deep.

ND-100 accessory current loads
@ 24 VDC

PA400: refer to PA400 data sheet DN-2405.

RA400Z: 0 mA standby, 10 mA maximum in alarm.

RTS451 and RTS451KEY: 0 mA standby, 7.5 mA maximum
in alarm.

ND-100R

Operating voltage range: 20 to 30 VDC, 24 VAC/VDC, 120/
240 VAC

auxiliary power (requires a separate auxiliary source).

Standby current: 300 µA @ 24 VDC (one communication
every 5 seconds with LED blink enabled).

Operating temperature range: 32° to 131°F (0° to 55°C).

Operating humidity range: 10% to 93% relative humidity (non-
condensing).

Storage temperature range: –22°F to +158°F (–30°C to
+70°C).

Duct air velocity: 100 to 4,000 feet/min (0.5 to 20.32 m/s).

Shipping weight: 3.90 lbs. (1.8 kg).

Dimensions: 14.75" (37 cm) length x 5.50" (14 cm) width x
2.75" (7 cm) deep.

ND-100R contact ratings

Alarm auxiliary contacts* (DPDT):

• 10 A @ 30 VDC.
• 10 A @ 277 VAC (0.75 power factor).
• 240 VA @ 249 VAC (0.4 power factor).
• 1/8 HP @ 120 VAC.
• 1/4 HP @ 240 VAC.

Supervisory contact (SPST):

• 2.0 A @ 30 VDC (resistive).

*Minimum switching current for auxiliary contact must be 100 mA
DC minimum @ 5 VDC.

ND-100R accessory current loads
@ 24 VDC

PA400:

refer to PA400 data sheet DN-2405.

RA400Z: 0 mA standby, 12 mA maximum in alarm.

RTS451 and RTS451KEY: 0 mA standby, 10 mA maximum
in alarm.

See table below for ND-100R current requirements.

PRODUCT LINE INFORMATION

ND-100

Addressable low-flow duct detector housing
with photoelectric smoke detector.

ND-100R

Addressable low-flow duct detector housing
with photoelectric smoke detector with DPDT
relay.

A5053FL

Replacement photoelectric sensor board.

A5067

Replacement power board (without relay).

A5060

Replacement power board (with relay).

ST-1.5

Metal sampling tube, duct widths 1' to 2' (

see

table on page 3 for metric lengths).

ST-3

Metal sampling tube, duct widths 2' to 4'.

ST-5

Metal sampling tube, duct widths 4' to 8'.

ST-10

Metal sampling tube, duct widths 8' to 12'.

RA400Z

Remote annunciator alarm LED.

RTS451

Remote test station. Mounts in single-gang
box. Includes red alarm LED and magnet test
switch.

RTS451KEY Key-activated remote test station.

F36-09-11

Replacement filters.

M02-04-00

Replacement test magnet.

S08-39-01

Replacement photo insect screen.

P48-61-00

Replacement end cap for plastic sampling
tube.

P48-21-00

Replacement end cap for metal sampling
tube.

T80-71-00

Replacement sampling tube.

7006crnt.tbl

RA400Z

RTS451

RTS451KEY

ND-100R current requirements (using no accessories)

Power supply voltage

20 – 30 VDC

24 VAC,

50/60 Hz

120 VAC,

50/60 Hz

220/240 VAC,

50/60 Hz

Max. standby current

26 mA

65 mA RMS

44 mA RMS

25 mA RMS

Max. alarm current

87 mA

182 mA RMS

52 mA RMS

30 mA RMS

Alarm response time

3 to 10 sec.

3 to 10 sec.

3 to 10 sec.

3 to 10 sec.

Power-up time

2 sec.

2 sec.

2 sec.

2 sec.