Wiring diagrams for nd-100, Inlet tube selection, Outside duct width inlet tube – Notifier ND-100R User Manual
Page 3

DN-7006 • 05/09/05 — Page 3 of 4
WIRING DIAGRAMS for ND-100
*NOTE: Inlet tube is required and must be purchased separately.
Order one inlet tube for each duct smoke detector ordered.
ND-100 Duct Smoke Detector
using a UL-Listed control panel
ND-100 Duct
Smoke Detector
with optional
RA400Z
ND-100 Duct
Smoke Detector
with RTS451/
RTS451KEY
NOTE:
For RTS451, Terminal 3
is not used. RTS451 does not
have a Terminal 6.
For RTS451KEY, Terminals 3
and 6 are not used.
ND-100 Detector Terminals
On to other
Detectors
on the Loop
ND-100
Detector
Terminals
6821wir3.wmf
6821wir2.wmf
6821wir1.wmf
Outside Duct Width
Inlet Tube*
Up to 2 feet (0.6096 m)
ST-1.5
2 to 4 feet (0.6096 to 1.2192 m)
ST-3
4 to 8 feet (1.2192 to 2.4384 m)
ST-5
8 to 12 feet (2.4384 to 3.6576 m)
ST-10
INLET TUBE SELECTION
6821inlt.tbl