DN-7006 • 05/09/05 — Page 3 of 4

WIRING DIAGRAMS for ND-100

*NOTE: Inlet tube is required and must be purchased separately.
Order one inlet tube for each duct smoke detector ordered.

ND-100 Duct Smoke Detector
using a UL-Listed control panel

ND-100 Duct
Smoke Detector
with optional
RA400Z

ND-100 Duct
Smoke Detector
with RTS451/
RTS451KEY

NOTE:

For RTS451, Terminal 3

is not used. RTS451 does not
have a Terminal 6.

For RTS451KEY, Terminals 3
and 6 are not used.

ND-100 Detector Terminals

On to other
Detectors
on the Loop

ND-100
Detector
Terminals

6821wir3.wmf

6821wir2.wmf

6821wir1.wmf

Outside Duct Width

Inlet Tube*

Up to 2 feet (0.6096 m)

ST-1.5

2 to 4 feet (0.6096 to 1.2192 m)

ST-3

4 to 8 feet (1.2192 to 2.4384 m)

ST-5

8 to 12 feet (2.4384 to 3.6576 m)

ST-10

INLET TUBE SELECTION

6821inlt.tbl