Notifier UDACT User Manual

Udact, Universal digital alarm communicator transmitter, General

Advertising
background image

dn-4867:b • 03/27/09 — Page 1 of 4

UDACT

Universal Digital Alarm
Communicator Transmitter

Annunciator Control Systems

dn-4867:b • D-160

General

The Universal Digital Alarm Communicator Transmitter

(UDACT) is designed for use on the Notifier NFS-320, NFS2-

640, NFS2-3030, NFS-640 and NFS-3030 Fire Alarm Control

Panels and on the NCA-2 and NCA Network Control Annunci-

ator. When used in conjunction with the NCA-2 network con-

trol annunciators the UDACT can report the status of all control

panels on NOTI•FIRE•NET™. The UDACT transmits system

status to UL listed Central Station Receivers via the public

switched telephone network.

NOTE: The UDACT can also be used with legacy panels. Please
refer to the UDACT manual for more information.

The UDACT is compact in size and may be mounted externally

in a separate cabinet. EIA-485 annunciator communications

bus and regulated 24-volt connections are required.
The UDACT is capable of transmitting the status of software

zones (Alarm and Trouble), System Trouble, Panel Off-Normal,

Supervisory, Bell Trouble, Low Battery, and AC Fail. The

UDACT is capable of transmitting all of the zone and point sta-

tus associated with each panel.
When the UDACT is used with the , NFS-3030, NFS2-3030,

and NCA-2 it is capable of reporting up to 2,040 points.

Reporting may be in the form of points or zones (refer to the

UDACT manual for specific reporting parameters). The first

568 points transmitted may be programmed for a variety of

types, including fire, waterflow, supervisory, etc. Remaining

points transmitted are for fire alarm only.

NOTE: Descriptions regarding point capacity, listed above, are for
receivers which receive in Ademco Contact ID format. See chart
on page 2 for compatible receivers.

Features

• Maximum of 14 point trouble messages transmitted per

hour.

• Dual phone lines.
• Dual telephone line voltage detect.
• Surface Mount Technology.
• Compact in size: 6.75" x 4.25" (17.145 x 10.795 cm).
• Built-in programmer.
• Built-in 4-character red 7-segment LED display.
• Manual Test Report function.
• Manual Transmission Clear function.
• Mounts in a separate enclosure (ABS-8RB or UBS-1).
• Communicates vital system status including:

Independent zone fire alarm.
Independent zone non-fire alarm.
Independent zone trouble.
Independent zone supervisory.
AC (mains) Power Loss (programmable).
Low Battery and Earth Fault.
System Off-Normal.
12 or 24 hour test signal.
Abnormal Test Signal per new UL requirements.
EIA-485 Communication Bus Failure.

• Annunciation of UDACT Troubles including: loss of phone

lines, communication failure with either Central Station, total

communications failure.

• Troubleshoot Mode converts keypad to DTMF touchpad.
• Individual LEDs for: Power, EIA-485 Loss, Manual Test,

Kissoff, Comm Fail, Primary Line Seize, Secondary Line

Seize and Modem Communications.

• Open Collector relay driver for Total Communications Fail-

ure or UDACT trouble.

• Real-time clock.
• Extensive transient protection.
• Simple EIA-485 interface to host panel.

Agency Listings and Approvals

In some cases, certain modules may not be listed by certain

approval agencies, or listing may be in process. Consult fac-

tory for latest listing status.
• UL Listed: S635
• ULC Listed: CS100 Vol. VII
• MEA: 328-94-E; 317-01-E3
• CSFM: 7300-0028:174; 7165-0028:214; 7165-0028:224;

7170-0228:216; 7170-0028:223; 7165-0028:243, 7170-

0028:244

• INDUSTRY CANADA: 2132 6030 A
• FCC: 1W6-USA-20723-AL-E
• FM Approved

Communication Formats

• 3+1 Standard

• 4+1 Standard

• 4+2 Standard

• 4+1 and 4+2 Ademco Express

• Ademco Contact ID

UDACT

48

67ud

ac.w

mf