Type mode feature, Electrical specifications, Ordering information – Notifier UDACT User Manual

Page 2

Advertising
background image

Page 2 of 4 — dn-4867:b • 03/27/09

NOTE: Ademco Contact ID must be used for independent zone
reporting.

Type Mode Feature

Ademco Contact ID format only) Use Type Mode to identify

reports to Central Station as:
• Fire Alarm

• Burglary

• Supervisory

• 24 hour Non-Burglary

• Pull Station

• High Temperature

• Heat Detector

• Low Temperature

• Waterflow

• Low Water Pressure

• Duct Detector

• Low Water Level

• Flame Sensor

• Pump Failure

• Smoke Zone

Electrical Specifications

Standby current: 40 mA.
Current while communicating: 75 mA.
Maximum current while communicating and with open collec-
tor output activated

: 100 mA.

Voltage: Regulated 24 volts. Range: 21.2 to 28.2 volts.

Ordering Information

UDACT: Universal Digital Alarm Communicator Transmitter.

Includes operating and programming instructions, and mount-

ing hardware.
MCBL-7: DACT phone cord, 7 ft (2.13 m) long (two required).
ABS-8RB: Metal enclosure for externally mounting UDACT

up to 6,000 ft./1828.8 m from host FACP. 9.94" H x 4.63" W x

2.50" D (cm: 25.248 H x 11.760 W x 6.350 D).
UBS-1: Metal enclosure. Includes viewing window and

optional relay mounting capability.
R-10E: SPDT Form-C relay. Contacts rated for 10 A @ 115

VAC. Connects to open collector relay driver.
R-20E: DPDT Two Form-C relays. Contacts rated for 10A @

115 VAC. Connects to open collector relay driver.
FBD-1: Ferrite bead kit. Use for remote mounting only.
ROM1-UDACT: EPROM upgrade kit.

ABS-8RB

for remote mounting

[9.94”(25.2476cm)H x

4.63”(11.7602cm)W x

2.5”(6.35cm)D]

515

55

ab

s.w

mf

4867ubs.wmf

UDACT

shown in UBS-1