7 analog input configuration – Horner APG XL7 OCS User Manual

Page 87

Advertising
background image

XL7 User Manual

The Output State On Controller Stop group box contains items to allow the user to specify how the

remaining digital outputs behave when the controller is stopped. These items can either hold their value

or default to some value when the controller is stopped.

15.7 Analog Input Configuration

The following figure illustrates the Analog Input Configuration dialog.

Figure 15.5 – Analog Input Configuration Dialog

The Channel x drop down windows allow the user to specify the mode for each analog input to operate.

The Channel x drop down windows are enabled/disabled according to which model is being configured.

All of the models have the following modes available:

-

0..10V

-

0..20mA

-

4..20mA

On model 005, all channels (1-4) also have the following modes available:

-

100mV

-

PT100 DIN RTD, 1/20°c

-

Type J Thermocouple, 1/20°c

-

Type K Thermocouple, 1/20°c

-

Type N Thermocouple, 1/20°c

-

Type T Thermocouple, 1/20°c

-

Type E Thermocouple, 1/20°c

-

Type R Thermocouple, 1/20°c

-

Type S Thermocouple, 1/20°c

-

Type B Thermocouple, 1/20°c

The Filter Constant provides filtering to all channels.

Page 87 of 110