5. Set the ‘Enable AutoRun’ option to YES if the controller needs to be placed in RUN mode
automatically after automatic restore of data or AutoLoad operation.
16.3 Backup / Restore Data
Selecting this option brings up a screen having four operations:
-
Backup OCS Data.
-
Restore OCS Data.
-
Clear Backup Data.
-
Exit
Figure 16.2 – Backup / Restore Data
Backup OCS Data:
When initiated, this will allow the user to manually copy Battery-Backed RAM contents on to the
onboard FLASH memory of the OCS. This will have the effect of backing up all the registers and
controller settings (Network ID, etc.) that would otherwise be lost due to a battery failure.
%SR164.4 is set to 1 when backup operation is performed.