C.5 net services tab – Campbell Scientific NL240 Wireless Network Link Interface User Manual

Page 62

Advertising
background image

Appendix C. NL240 Settings

number of the serial server is set. Typically, it is not necessary to change this

entry from its default. (range 1..65535)

SDC Address

Communication with the datalogger via the CS I/O port is done using SDC

(Synchronous Device Comms). The datalogger will address the devices with

which it wishes to communicate using an SDC address. The CS I/O port can

be configured to respond to SDC address 7, 8, 10, or 11.

CS I/O TCP Timeout

This setting, in units of seconds, will determine how fast the CS I/O serial

server will time out if no activity is detected. Set to 0 for no time-out (not

recommended). (range 0..999)

CS I/O PakBus Beacon Interval

This setting, in units of seconds, governs the rate at which the NL240 will

broadcast PakBus® messages on the associated port in order to discover any

new PakBus neighboring nodes. It will also govern the default verification

interval if the value of the Verify Interval setting for the associated port is zero.

CS I/O PakBus Verify Interval

This setting specifies the interval, in units of seconds, that will be reported as

the link verification interval in the PakBus® hello-transaction messages. It

will indirectly govern the rate at which the NL240 will attempt to start a hello

transaction with a neighbor if no other communication has taken place within

the interval.

CS I/O Modbus Timeout

This setting determines how long the MODBUS/TCP to MODBUS/RTU

gateway will wait for an answer from the MODBUS slave device(s) attached to

the CS I/O port. If no answer is received within the timeout period, the

MODBUS/TCP server will reply to the MODBUS/TCP client with error code

0x0B (Target Device Failed to Respond). (milliseconds)

C.5 Net Services Tab

Telnet

Enables/Disables the telnet service.

Telnet Port Number

The default TCP port number for the configuration monitor telnet session is 23.

This entry makes it possible for the user to change the telnet session port

number if desired. Typically, it is not necessary to change this entry from its

default. (range 1..65535)