3 building and sending data frames, 4 using the interrupt function, Building and sending data frames – Campbell Scientific SDM-CAN Datalogger to CANbus Interface User Manual

Page 40: Using the interrupt function

Advertising
background image

SDM-CAN Datalogger-to-CANbus Interface

13: 1.0

Mult

14: 0.0

Offset


*Table 2 Program
02: 0.0000 Execution

Interval

(seconds)


*Table 3 Subroutines

End Program

The default setting for the SDM-CAN internal software switches
is 0. The switches must be set by using the data type 32
parameter to enable data transmission. Also remember to check
the jumper settings inside the SDM-CAN if enabling
transmission, as the default setting is for transmission to be
disabled in hardware.

NOTE

3.5.3 Building and Sending Data Frames

The following table shows the parameters used for the process of using a series
of P118s to build a dataframe and then use a further call with data type set to
26 to define part of the working buffer as a remote frame response:

Input Loc Value

Data
type

Start Bit

nbits

Dec

Hex

Indexed

64 bit Frame

Un-initialized frame>>

0x12abcdef12345678

170

0xaa

7

5

N

8

Loaded into frame>>

0x0000000000000aa0

1234 0x4d2

13 17

N

16

Ored

into

frame>>

0x0000000004d20aa0

65535 0xffff 13 31

N

7 Ored

into

frame>>

0x0000001fc4d20aa0

171 0xab

13

8

Y 8

Ored

into

frame>>

0xab00001fc4d20aa0

X

X

26

28

Y

32

Remote Response Frame>>

0x0ab00001 32 bit frame

3.5.4 Using the Interrupt Function

By indexing (‘--‘) the No. of bits parameter, when a new value that an
instruction refers to is received the SDM-CAN I/O interrupt is enabled. This
can be used to set a control port high and run an interrupt subroutine. An
example of using the interrupt function is shown below.

32