Section 5. Programming the Datalogger

5-16

*Table 1 Program

01: 2

Execution Interval (seconds)

;if flag one is not set then set up the serial mode and filter.

1: If Flag/Port (P91)

1:

21

Do if Flag 1 is Low

2:

30

Then Do

;set serial mode to DTR, RTS always set, ignore CTS, 1 stop bit no parity,
;8 bit data length, 9600 baud and no handshake delay.

2: SDM-SIO4 (P113)

1:

1

Reps

2:

0

Address

3:

1

Send/Receive Port 1

4:

2049

Command

5:

3146

1st Parameters

6:

0

2nd Parameters

7:

0

Values per Rep

8:

0000

Loc [ _________ ]

9:

1.0

Mult

10: 0.0

Offset

;set up a simple filter 1999 search for floating point number.

3: SDM-SIO4 (P113)

1:

1

Reps

2:

0

Address

3:

1

Send/Receive Port 1

4:

2054

Command

5:

1999

1st Parameters

6:

0

2nd Parameters

7:

0

Values per Rep

8:

0000

Loc [ _________ ]

9:

1.0

Mult

10: 0.0

Offset

;the set up filter command requires a delay of 4ms, the nearest we can get
;is 10ms with P22.

4: Excitation with Delay (P22)

1:

1

Ex Channel

2:

0

Delay W/Ex (units = 0.01 sec)

3:

1

Delay After Ex (units = 0.01 sec)

4:

0

mV Excitation

;set flag one high so the above will only be done once.

5: Do (P86)

1:

11

Set Flag 1 High

;end of serial and filter setup.