Configuration, Ups settings – American Power Conversion 5000VA User Manual

Page 16

Advertising
background image

12

Smart-UPS 5000 VA 208/230 Vac Tower/Rack-Mount 5U User Manual

Configuration

UPS settings

Settings are adjusted through PowerChute software or optional SmartSlot accessory cards.

Function

Factory

Default

User Selectable

Choices

Description

Automatic
Self-Test

On startup and
every 14 days

(336 hours)
there after

• On startup and every

7 days (168 hours)

there after

• On startup and every

14 days (336 hours)

there after

• On startup only
• No self-test

Set the interval at which the UPS will execute a
self-test.

UPS ID

UPS_IDEN

Up to eight characters
(alphanumeric)

Uniquely identify the UPS, (i.e. server name or
location) for network management purposes.

Date of Last

Battery
Replacement

Manufacture

Date

mm/dd/yy

Reset this date when you replace the battery

module.

Minimum Capacity

Before Return from
Shutdown

0 percent

• 0%
• 15%
• 30%
• 45%

• 60%
• 75%
• 90%

Specify the percentage to which batteries will

be charged following a low battery shutdown
before powering connected equipment.

Voltage Sensitivity
The UPS detects
and reacts to line

voltage distortions
by transferring to
battery operation to

protect the
connected
equipment.

High sensitivity

Brightly
illuminated: high
sensitivity
Dimly illuminated:
medium sensitivity
No illumination:

low sensitivity

Adjust by pressing the VOLTAGE SENSITIVIY
switch (rear panel). Use a pointed object, (such
as a pen) to do so.
Note: In situations of poor power quality, the
UPS may frequently transfer to battery
operation. If the connected equipment can

operate normally under such conditions, reduce
the sensitivity setting to conserve battery
capacity and service life.

Alarm Delay
Control

Enable

• Enable
• Mute
• Disable

Mute ongoing alarms or disable all alarms.

Shutdown Delay

90 seconds

• 0 s
• 90 s
• 180 s
• 270 s

• 360 s
• 450 s
• 540 s
• 630 s

Set the interval between the time when the UPS
receives a shutdown command and actual
shutdown.