Specifications, Installation, Rack-mount configuration – American Power Conversion 5000VA User Manual

Page 6

Advertising
background image

2

Smart-UPS 5000 VA 208/230 Vac Tower/Rack-Mount 5U User Manual

Specifications

NOTE: The model and serial numbers are located on a small, rear panel label. For some models, an additional label

is located on the chassis under the front bezel.

Installation

Rack-mount configuration

This unit is intended for mounting in a four post rack. To order a two post rack-mount kit contact your dealer or

refer to the APC Web site, www.apc.com.
The UPS and the battery modules are heavy. Remove the battery modules to lighten the UPS during

installation. Refer to the battery removal instructions on the packaging.
Install rack-mount brackets and rail cleats

Four screws must be used to secure each rail bracket and rail cleat to the UPS. One rack-mount bracket and one

rail cleat must be secured to the both sides of the UPS.

Temperature

Operating

Storage

32

°

to 104

°

F (0

°

to 40

°

C)

5

°

to 86

°

F (-15

°

to 30

°

C) charge the UPS battery every six months

86

°

to 113

°

F (30

°

to 45

°

C) charge the UPS battery every three months

This unit is intended for indoor use

only. Select a location sturdy enough

to handle the weight.
Do not operate the UPS where there

is excessive dust or the temperature

or humidity are outside the specified

limits.
Environmental factors impact battery

life. High temperatures, poor utility

power, and frequent, short duration

discharges will shorten battery life.

Maximum

Elevation

Operating

Storage

6562 ft (2,000 m)
50,000 ft (15,240 m)

Humidity

0 to 95% relative humidity, non-condensing

Weight

215 lbs (98 kg) with battery module
107 lbs (49 kg) without battery module
27 lbs (12 kg) each battery module

215 lbs (98 kg)

4x

4x

Rack-mount bracket

four post rack-mount position

Rail cleat

Advertising