American Power Conversion 5000VA User Manual

Page 17

Advertising
background image

Smart-UPS 5000 VA 208/230 Vac Tower/Rack-Mount 5U User Manual

13

Low Battery
Warning
PowerChute
software interface
provides automatic,

unattended
shutdown when
approximately two
minutes of battery

operated run time
remains.

2 minutes

LED is located
on rear panel

Brightly
illuminated:

low battery warning
level of about 2 minutes

Dimly illuminated:
low battery

warning level of about
5 minutes

No illumination:
low battery warning

level is about 8 minutes

The low-battery warning beeps are continuous
when two minutes of run time remain.
To change the default interval setting, use a
pointed object such as a pen to press the
VOLTAGE SENSITIVIY switch (rear panel),

while

pressing the

button, (front display).

Change the low battery warning interval setting
to the time that the operating system or system
software requires to safely shut down.

Synchronized
Turn-on Delay

0 seconds

• 0 s
• 60 s
• 120 s
• 180 s

• 240 s
• 300 s
• 360 s
• 420 s

Specify the time the UPS will wait after the
return of utility power before start up, (to avoid
branch circuit overload).

High Transfer Point

208 V models:
225 Vac

230 V models:
253 Vac

• 225 Vac
• 229 Vac

• 253 Vac
• 257 Vac

• 233 Vac
237 Vac

• 261 Vac
• 265 Vac

To avoid unnecessary use of the battery where
utility voltage is chronically high, set the high

transfer point higher if the connected
equipment can tolerate this condition.

Low Transfer Point

208 V models:
182 Vac

230 V models:
208 Vac


• 182 Vac
• 178 Vac

• 196 Vac
• 200 Vac


• 174 Vac
• 170 Vac

• 204 Vac
• 208 Vac

To avoid unnecessary use of the battery where
utility voltage is chronically low, set the low

transfer point lower if the connected equipment
can tolerate this condition.

Output Voltage
230 V models

230 Vac

• 220 Vac
• 230 Vac

• 240 Vac

Set the output voltage of the UPS.

Function

Factory

Default

User Selectable

Choices

Description