Smart-UPS 5000 VA 208/230 Vac Tower/Rack-Mount 5U User Manual

17

Maintenance, Transport, and Service

Replace battery modules

This UPS has easy-to-replace, hot-swappable battery modules. Replacement is a safe procedure, isolated from

electrical hazards. You may leave the UPS in the rack and connected equipment on during the replacement

procedure.
Once the batteries are disconnected the connected equipment is not protected from power outages.
Refer to the appropriate replacement battery user manual for battery module installation instructions. See your

dealer or contact APC at www.apc.com for information on replacement battery modules.

Be sure to deliver the spent battery(s) to a recycling facility or ship it to APC in the

replacement battery packing material.

4x

Remove spent batteries from the UPS

Install new batteries

Pull the battery disconnect cords
attached to the battery connectors.

DO NOT pull the battery cables to
disconnect the batteries.

Battery

disconnect

cord

Open battery doors