3. MODBUS/RTU INTERFACE (NOT TCP)

3.1. Surpported MODBUS Function Codes

Function
Code

Function

Description

1(0x01)

Read Coils

Read output bit

2(0x02)

Read Discrete Inputs

Read input bit

3(0x03)

Read Holding Registers

Read output word

4(0x04)

Read Input Registers

Read input word

5(0x05)

Write Single Coil

Write one bit output

6(0x06)

Write Single Register

Write one word output

8(0x08)

Diagnostics

Read diagnostic register

15(0x0F)

Write Multiple Coils

Write a number of output bits

16(0x10)

Write Multiple registers

Write a number of output words

23(0x17)

Read/Write Multiple registers

Read a number of input words /Write a number of output words

Refer to MODBUS APPLICATION PROTOCOL SPECIFICATION V1.1a

3.1.1.

1 (0x01) Read Coils

This function code is used to read from 1 to 2000 contiguous status of coils in a remote device. The Request PDU
specifies the starting address, i.e. the address of the first coil specified, and the number of coils. In the PDU Coils are
addressed starting at zero. Therefore coils numbered 1-16 are addressed as 0-15. The coils in the response message are
packed as one coil per bit of the data field. Status is indicated as 1= ON and 0= OFF.

Request

Field name

Example

Function Code

0x01

Starting Address Hi

0x10

Starting Address Lo

0x00

Quantity of Outputs Hi

0x00

Quantity of Outputs Lo

0x0A

Response

Field name

Example

Function Code

0x01

Byte Count

0x02

Output Status

0x55

Output Status

0x02

In case of address 0x1015~0x1000 output bit value: 10101010_01010101.