FnBus PIO N/A

Page 14

3.1.7.

8 (0x08) Diagnostics

MODBUS function code 08 provides a series of tests for checking the communication system between a client
( Master) device and a server ( Slave), or for checking various internal error conditions within a server.

The function uses a two–byte sub-function code field in the query to define the type of test to be performed. The server
echoes both the function code and sub-function code in a normal response. Some of the diagnostics cause data to be
returned from the remote device in the data field of a normal response.

Request

Field name

Example

Function Code

0x08

Sub-Function Hi

0x00

Sub-Function Lo

0x00

Data Hi

0x11

Data Lo

0x22

Response

Field name

Example

Function Code

0x08

Sub-Function Hi

0x00

Sub-Function Lo

0x00

Data Hi

0x11

Data Lo

0x22

Sub-function 0x0000(0) Return Query Data

The data passed in the request data field is to be returned (looped back) in the response.

The entire response message should be identical to the request.

Sub-function

Data Field (Request)

Data Field (Response)

Description

0x0000(0)

Any

Echo Request Data

Sub-function 0x0001(1) Restart Communications Option

The remote device could be initialized and restarted, and all of its communications event counters are cleared.

Especially, data field 0x55AA make the remote device to restart with factory default setup of EEPROM.

Sub-function

Data Field (Request)

Data Field (Response)

Description

0x0001(1)

0x0000 or 0xFF00

Echo Request Data

Reset

0x0001(1)

0x55AA

Echo Request Data

Reset with Parameter
default

1)

0x0001(1)

0x55BB

Echo Request Data

Erase CoDeSys
program ²

)

1) NA-9379 and slot parameter will be the factory defaults value.

2) If all program is erased, NA-9379 change Stop mode. (about 10 sec)

Sub-function 0x000A(10) Clear Counters and Diagnostic Register

The goal is to clear all counters and the diagnostic register. Counters are also cleared upon power–up.

Sub-function

Data Field (Request)

Data Field (Response)

Description

0x000A(10)

0x0000

Echo Request Data