3.1.2.

2 (0x02) Read Discrete Inputs

This function code is used to read from 1 to 2000 contiguous status of discrete inputs in a remote device. The Request
PDU specifies the starting address, i.e. the address of the first input specified, and the number of inputs. In the PDU
Discrete Inputs are addressed starting at zero. Therefore Discrete inputs numbered 1-16 are addressed as 0-15.

The discrete inputs in the response message are packed as one input per bit of the data field.

Status is indicated as 1= ON; 0= OFF.

Request

Field name

Example

Function Code

0x02

Starting Address Hi

0x00

Starting Address Lo

0x00

Quantity of Inputs Hi

0x00

Quantity of Inputs Lo

0x0A

Response

Field name

Example

Function Code

0x02

Byte Count

0x02

Input Status

0x80

Input Status

0x00

- In case of address 0x0015~0x0000 input bit value: 00000000_10000000.

3.1.3.

3 (0x03) Read Holding Resgisters

This function code is used to read the contents of a contiguous block of holding registers in a remote device. The
Request PDU specifies the starting register address and the number of registers.

The register data in the response message are packed as two bytes per register, with the binary contents right justified
within each byte. For each register, the first byte contains the high order bits and the second contains the low order bits.

Request

Field name

Example

Function Code

0x03

Starting Address Hi

0x08

Starting Address Lo

0x00

Quantity of Register Hi

0x00

Quantity of Register Lo

0x02

Response

Field name

Example

Function Code

0x03

Byte Count

0x04

Output Register#0 Hi

0x11

Output Register#0 Lo

0x22

Output Register#1 Hi

0x33

Output Register#1 Lo

0x44

- In case of address 0x0800, 0x0801 output register value: 0x1122, 0x3344.