Calibration level, Type of adopted program, Programs of ramp and soak – NOVUS Controller N960 User Manual

Page 4: Complete level and ramp program, Program tolerance function - ptol, Programs with few segments

Advertising
background image

N960 Controller

NOVUS AUTOMATION

4/6

Ai

ky

A2ky

Alarm

HYsteresis

ALARM HYSTERESIS 1 AND 2: Defines the

difference between the measured value when the

alarm is activated and the value that is deactivated.

A1bl
A2bl

Alarm Blocking

Initial Alarm block:
Yes

Enables initial block

No

Does not enable initial block

Pr.ty

Program Type

Type of program to be adopted by controller:
none

Does not adopt any type of program

rate

Adopts ramp to level function

Prog

Adopts complete Ramp and Level

program.

CALIBRATION LEVEL
All types of input and output are calibrated at the factory. If recalibration

is required, it must be performed by a specialist. If this cycle is

accessed accidentally, pass through all parameters without making

changes to their values.

pass

Password. Input of the Access Password.
This parameter is presented before the protected

cycles. See item Protection of Configuration.

inL(

Input Low Calibration. Enter the value

corresponding to the low scale signal applied to the

analog input.

ink(

Input High Calibration. Enter the value

corresponding to the full scale signal applied to the

analog input.

0vL(

Output Low Calibration. Enter of the value

measured at the analog output.

0vk(

Output High Calibration. Enter of the value

measured at the analog output.

rstr

Restore. Restores the factory calibration for all input,

analog output and remote SP, disregarding

modifications carried out by the user.

(j

Cold Junction. Adjusts the of cold junction

temperature value.

Pas.(

Password. Allows defining a new access password,

always different from zero.

Prot

Protection. Sets up the Level of Protection. See

Table 2.

TYPE OF ADOPTED PROGRAM

Two forms of program execution are available in the controller. The

Program Type (Pr.Ty) parameter allows user to choose between

Ramp to Level (rate) and a complete Ramp and Level program

(Prog). User can also choose to not execute any type of program

(none).

PROGRAMS OF RAMP AND SOAK

Available when the Rate option in the Pr.Ty parameter is selected.
The controller allows the process temperature to vary gradually from an

initial value until a specified final value, determining a Ramp-like behavior.

The initial value of the Ramp will always be the process initial

temperature (PV). The final value will always be the value defined in SP.
User determines the increase (or decrease) speed of the ramp in the

“rAtE” parameter, which defines a temperature variation rate in degrees

per minute. In order to disable the Ramp function, program the value 0.0.
When the SP value is reached, the controller starts to control the

process in SP (level) by an interval of time or indefinitely.
The t SP parameter, adjustable between 0 and 9999 minutes,

determines the level duration. At the end of the level, the control is

disabled (run = no) and all outputs are turned off. With value 0 in t SP

the control continues indefinitely without time limit.

As alarm can be associated at the end of the level. The End.t Alarm

Function determines that an alarm is activated at the end of the level.

Valid only with t sp ≠ 0.

Fig. 2 - Level Ramp Function

Upon returning from a power failure, the controller automatically restarts

the execution of the Ramp to Level function. If the PV value is smaller

than the SP value, the Ramp restarts at this point until it reaches SP. If

the temperature is equal to SP, Level execution is restarted.

COMPLETE LEVEL AND RAMP PROGRAM
Available when the Prog option is selected in the Pr.Ty parameter.
The controller allows to elaborate one temperature ramp and level

program. This program is created from the SP value definition and time

intervals, defining up to nine (9) program segments. The figure below

shows a program model with 9 segments:

Fig. 03 - Example of a ramp and level program

The program created is permanently stored in the controller’s memory.

It can be modified freely, executed when necessary and repeated as

often as necessary.
In order to execute a program:

1- Turn off outputs (rvn= NO);
2- Enable execution of parameter E.Pr= yes;
3- Trigger start turning on outputs: (rvn= yes).

Once a program is initiated, the controller starts to automatically

generate the SP values defined for each program segment. SP

adjustment in the indication screen remains blocked.

PROGRAM TOLERANCE FUNCTION - PTOL
The “PtoL” program tolerance program defines the maximum error

limit between the PV and SP values during program execution. If this

limit is exceeded, the timing of the segment (Pt1…Pt9) is interrupted

until the error is within the established tolerance. With a value > 0, the

user indicates in the program that priority must be given to PV

regarding the determined time values.
If zero tolerance (Ptol = 0) is programmed, the controller executes

the program defined without considering eventual errors between PV

and SP. Thus, the user defines that the priority be given to the program

execution time.

PROGRAMS WITH FEW SEGMENTS
In order to execute a program with a smaller number of segments, just

program 0 (zero) for the time interval that follows the last segment of

the desired program.

SP

TIME

T1

T2

T3

PSP0

PSP1

PSP2

PSP3

T4=0

Fig. 04 - Example of a program with only 3 segments