NOVUS Controller N1100 User Manual

Controller n1100

Advertising
background image

NOVUS AUTOMATION

1/8

Controller N1100

UNIVERSAL PROCESS CONTROLLER – INSTRUCTIONS MANUAL V2.1x

PRESENTATION

The N1100 is a process controller incorporating a PID algorithm and
universal inputs (sensor and standard signals) and outputs (logical,
relay and analog outputs). It holds in one single instrument all de main
features that are needed for the vast majority of industrial processes.

SAFETY SUMMARY

The symbols below are used on the equipment and throughout this
document to draw the user’s attention to important operational and
safety information.

CAUTION or WARNING:

Read complete instructions prior

to installation and operation of the

unit.

CAUTION or WARNING:

Electrical Shock Hazard

All safety related instructions that appear in the manual must be
observed to ensure personal safety and to prevent damage to either
the instrument or the system. If the instrument is used in a manner
not specified by the manufacturer, the protection provided by the
equipment may be impaired.

OVER-TEMPERATURE PROTECTION

When designing any control system it is essential to consider what
will happen if any part of the system should fail. In temperature
control applications the primary danger is one in which the heating
remains constantly on. In any application where physical injury or
destruction of equipment might occur, it is recommend to install an
independent protection equipment, with a separate temperature
sensor, to disable the heating circuit in case of overheating. Please
note that the alarm relays within the controller will not give protection
under all failure conditions.

INSTALLATION

Insert the unit into the panel cut-out and slide the mounting clamp
from the rear to a firm grip at the panel.

ELECTRICAL CONNECTIONS

All electrical connections are made to the screw terminals at the rear
of the controller. They accept wire sizes from 0.5 to 1.5 mm2 (16 to
22 AWG). The terminals should be tightened to a torque of 0.4 Nm
(3.5 lb in).

To minimize the pick-up of electrical noise, the low voltage DC
connections and the sensor input wiring should be routed away from
high-current power conductors. If this is impractical, use shielded
cables. In general, keep cable lengths to a minimum.

Figure 1 - Backpannel terminals

Power Wiring

If high voltage is applied

to a low voltage input,

irreversible damage will

occur

Figure 2 – High and Low Voltage AC power wiring

Thermocouple and Voltage (Volts and mV) input connect as in

Figure 3.

T/C, 0-50mV, 0-5V

Pt100

Figure 3 – T/C and Voltage wiring

Figure 4 - RTD input wiring

Advertising