Controller N1100

NOVUS AUTOMATION

3/8

CONFIGURATION

INPUT TYPE SELECTION

Select the input type (in parameter “tYPE

tYPE

tYPE

tYPE”) from Table 1 below.

TYPE

CODE

CHARACTERISTICS

J

0

0

0

0

Range: -50 to 760 °C (-58 to 1400 ºF)

K

1

1

1

1

Range: -90 to 1370 °C (-130 to 2498 ºF)

T

2

2

2

2

Range: -100 to 400 °C (-148 to 752 ºF)

N

3

3

3

3

Range: -90 a 1300 °C (-130 a 2372 ºF)

R

4

4

4

4

Range: 0 a 1760 °C (32 a 3200 ºF)

S

5

5

5

5

Range: 0 to 1760 °C (32 to 3200 ºF)

Pt100

6

6

6

6

Range: -199.9 to 530.0 °C (-328.0 to 986.0 ºF)

Pt100

7

7

7

7

Range: -200 to 530 °C (-328 to 986 ºF)

4-20 mA

8

8

8

8

J linearization. Programmable range: -110 to 760 °C

4-20 mA

9

9

9

9

K linearization. Programmable range: -150 to 1370 °C

4-20 mA

10

10

10

10

T linearization. Programmable range: -160 to 400 °C

4-20 mA

11

11

11

11

N Linearization. Programmable range: -90 a 1370 °C

4-20 mA

12

12

12

12

R Linearization. Programmable range: 0 a 1760 °C

4-20 mA

13

13

13

13

S linearization. Programmable range: 0 to 1760 °C

4-20 mA

14

14

14

14

Pt100 linearization. Prog. Range:-200.0 to 530.0 °C

4-20 mA

15

15

15

15

Pt100 linearization Prog. Range:-200 to 530 °C

0-50 mV

16

16

16

16

Linear. Programmable indication -1999 to 9999

4-20 mA

17

17

17

17

Linear. Programmable indication -1999 to 9999

0-5 Vdc

18

18

18

18

Linear. Programmable indication -1999 to 9999

4-20 mA

19

19

19

19

Square Root Extraction

Table 1 - Input Types

OUTPUTS, ALARMS AND DIGITAL INPUTS CONFIGURATION

The controller input/output channels can assume multiple functions,
depending on configuration: control output, alarm output, digital
output, digital input, and PV or SV analog retransmission. These
channels are identified as I/O1, I/O2, I/O3, I/O4 and I/O 5.

The basic controller model comes loaded with:

I/O1 - relay output

I/O2 - relay output

I/O5 - analog output (0-20 or 4-20mA), pulse 10V max, digital I/O

The options available are:

I/O3 - 3rd relay (option 1)

I/O3 and I/O4 - 2 digital input/output (option 2)

Heater break protection (option 3).

The function code of each I/O can be selected among the options on
Table 2. Only valid function codes are displayed for each I/O (for
example, I/O1, which is a relay, can be configured with functions 0 to
5 only; on the other hand, I/05 can perform all 16 functions).

The description for the functions follows:

CODE 0 - No function. The I/O channel programmed with code 0
will not be used by the controller. It is available to be used by serial
communication as digital output.

CODES 1 to 4 - Alarm output - Available for all I/O channels. The
selected channel can be used as output to Alarms 1 to 4.

CODE 5 - PWM control output - Available for all I/O channels.

CODE 6 - Digital input - Standard for I/O5 and optional for I/O3 and
I/O4.

Closed : Manual control
Opened: Automatic control

CODE 7 - Digital input - Standard for I/O5 and optional for I/O3 and
I/O4. Start/Stop input (“rvn

rvn

rvn

rvn” : YES / no).

Closed : outputs enabled
Opened: outputs disabled

CODE 8 - Digital input - Standard for I/O5 and optional for I/O3 and
I/O4.

Closed: remote SP (4-20 mA in remote SP input)
Opened: main SP (internal programmed SV)

CODE

I/O TYPE

I/O FUNCTION

0

0

0

0

Digital Output

Digital Output to be set by the serial comm.

1

1

1

1

Digital Output

Alarm 1 Output

2

2

2

2

Digital Output

Alarm 2 Output

3

3

3

3

Digital Output

Alarm 3 Output

4

4

4

4

Digital Output

Alarm 4 Output

5

5

5

5

Digital Output

PWM Control Output

6

6

6

6

Digital Input

Automatic/Manual mode change

7

7

7

7

Digital Input

Run/Stop mode change

8

8

8

8

Digital Input

Select Remote Set Point Input

9

9

9

9

Digital Input

Executes/Holds selected ramp and soak profile

10

10

10

10

Digital Input

Enable/Disable R&S profile 1 selection

11

11

11

11

Analog Output

0 to 20mA Analog control output

12

12

12

12

Analog Output

4 to 20mA Analog control output

13

13

13

13

Analog Output

0 to 20mA PV retransmission

14

14

14

14

Analog Output

4 to 20mA PV retransmission

15

15

15

15

Analog Output

0 to 20mA SP retransmission

16

16

16

16

Analog Output

4 to 20mA SP retransmission

Table 2 - I/O channel functions

CODE 9 - Digital input - Standard for I/O5 and optional for I/O3 and
I/O4.

Opened: enables R&S program
Closed: holds R&S program (the program resumes when the
contact is opened again)

CODE 10 - Digital input - Standard for I/O5 and optional for I/O3 and
I/O4. Selects R&S program 1. Used to alternate between the main
Setpoint and a second Setpoint defined by the R&S program 1.

Closed : selects program 1
Opened: uses main Setpoint

CODE 11 - Analog control output - I/O5 only. 0-20 mA control
output.

CODE 12 - Analog control output - I/O5 only. 4-20 mA control
output.

CODES 13 to 16 - Analog retransmission. I/O5 only. Configures
I/O5 to output a 0-20 mA or 4-20 mA analog signal proportional to
PV or SP.

ALARM FUNCTIONS

The controller has 4 independent alarms. They can be programmed
to operate with nine different functions, represented in Table 3.

Open sensor

It is activated whenever the input sensor is broken or disconnected.

Event alarm

It activates alarm(s) in specific segments of the program.

Resistance fail

Detects a heater broken condition, by monitoring the load current
when the control output is activated. This alarm function requires an
optional device (option 3). Details of the "resistance fail" option can
be found in a specific documentation that is sent with the product
when the option is purchased.