Serial communication, Specifications, Warranty – NOVUS Controller N1100 User Manual

Page 8

Advertising
background image

Controller N1100

NOVUS AUTOMATION

8/8

SERIAL COMMUNICATION

The indicator can be supplied with an asynchronous RS-485 digital
communication interface for master-slave connection to a host
computer (master).

The indicator works as a slave only and all commands are started by
the computer which sends a request to the slave address. The
addressed unit sends back the requested reply.

Broadcast commands (addressed to all indicator units in a multidrop
network) are accepted but no reply is sent back in this case.

CHARACTERISTICS

RS-485 compatibility with two-wire connection from the host to up to
31 slaves in a multidrop network topology. Up to 247 units can be
addressed by the MODBUS RTU protocol. Maximum network
distance: 4,000 feet. Time of indicator disconnection: Maximum of 2
ms after the last byte.

Te communication signals are electrically isolated from the rest of the
instrument, and can be 1200, 2400, 4800, 9600, 19200, 38400, and
57600 bps.

Number of data bits: 8, without parity or pair parity

Number of stop bits: 1

Time to start response transmission: up to 100 ms after
acknowledging the command.

Protocol: MODBUS (RTU)

RS485 INTERFACE: ELECTRICAL CONNECTION

The RS-485 signals are:

D1 = D: Bidirectional data line

D0 =

D:

Inverted bidirectional data line

C = GND: Ground. Optional connection to improve communication

performance

SPECIFICATIONS

DIMENSIONS:.....................................................48 x 48 x 110 mm (1/16 DIN).
Approximate weight: 150 g

PANEL CUT-OUT:............................................45,5 x 45,5 mm (+0.5 -0.0 mm)

TERMINAL CONNECTION: .................18 screws accepting 6.3 mm fork lugs

POWER: 100 to 240 Vac/dc (±10 %), 50/60 Hz. Transient overvoltage: ±2 kV

Optional: ......................................................................... 24 Vac/dc ±10 %
Max. Consumption: ........................................................................... 9 VA

ENVIRONMENTAL CONDITIONS:.................................................... 5 to 50 °C

Relative humidity (maximum): 80 % up to 30 ºC. For temperatures
above 30 ºC, decrease 3 % per ºC. Installation category II. Pollution
degree 2. Altitude < 2000 m.

INPUT ................................. Keyboard selection of input type (refer to Table 1)

Internal resolution: ............................................................... 19500 levels
Display resolution: .............................12000 levels (from -1999 to 9999)
Input sample rate:.................................................................5 per second
Accuracy: ..................Thermocouples J, K and T: 0.25 % of span

±

1 ºC

............................................Thermocouple N, R, S: 0.25 % of span

±

3 ºC

...................................................................................Pt100: 0.2 % of span
................................................ 4-20 mA, 0-50 mV, 0-5 Vdc: 0.2 % of span

Input impedance:............. 0-50 mV, Pt100 and thermocouples: >10 M

.............................................................................................. 0-5 V: >1 M

............................................................. 4-20 mA: 15

(+2 Vdc @ 20 mA)

Pt100 measurement: ............................................ standard (

α

=0.00385).

Excitation current:..............................................0.170 mA. 3-wire circuit,
cable resistance compensation.

All input types are factory calibrated according to IEC-584 for
thermocouples and IEC-751 for Pt100.

ANALOG OUTPUT (I/O5): .......................... 0-20 mA or 4-20 mA, 550

max.

....................................................................................1500 levels, Isolated
..................................................control output or PV or SP retransmission

CONTROL OUTPUT: ................................ Relays SPST-NO (I/O1 AND I/O2):
1.5 A / 240 Vac.

............................................................ Relays SPDT (I/O3): 3 A / 250 Vac
..................................Logic pulse for SSR drive (I/O5): 10 V max / 20 mA
................... Logic pulse for SSR drive (I/O3 AND I/O4): 5 V max / 20 mA

SECOND ANALOG INPUT: ...................4-20 mA remote set point (standard).

This feature requires an external shunt resistor, provided with the instrument,
to be connected to terminals 9 and 10.

EMC : ........................................... EN 61326-1:1997 and EN 61326-1/A1:1998

SAFETY:........................................ EN61010-1:1993 and EN61010-1/A2:1995

PROGRAMMABLE PWM CYCLE FROM 0.5 SEC. AND 100 SEC.;

START UP 3 SECONDS AFTER POWER UP.

ORDERING INFORMATION

N1100 -

3R -

485 -

24V

A

B

C

D

A: Series model:

N1100;

B: Optionals:

blank (standard controller);
3R (3 relays);
HBD (Heater Break Detection);
DIO (digital I/O);

C: Digital communication: blank;

485 (RS485, Modbus protocol);

D: Voltage rating:

blank (100 to 240 Vac);
24V (24Vac/dc).

WARRANTY

This product is covered by a 12-month warranty provided the purchaser
presents the sales receipt and the following conditions are met:

Products are covered for one year from the original date of

purchase. Please retain the dated sales receipt as evidence of the
date of purchase. You will need it for any warranty service

Within this period, warranty against defects in material and

workmanship under normal use is free of charge.

For repair, send the product and the sales receipt to our address.

Expenses and transportation risks are under the purchaser’s
responsibility.

This warranty does not cover any damage due to accident,

misuse, abuse, or negligence.

Advertising