Problems with the controller, Finding the controller’s version and serial number, Specifications – NOVUS Controller N480D User Manual

Page 5: Outa / outc relay spst-na: 1.5 a / 240 vac, Outb voltage pulse for ssr, 12 v max. / 20 ma, Outd (rar) 0-20 ma or 4-20 ma, 550 ( max. 31000 levels, isolated, Model identification

Advertising
background image

N480D Controller

NOVUS AUTOMATION

5/6

PROMPT

TYPE

ACTION

Off

Disabled

Output is not used as alarm.

Lo

Minimum

value

(Low)

SPAn

PV

ON

Ki

Maximum

value

(High)

SPAn

PV

ON

Dif

Differential

(diFerential)

SV

PV

SV + SPAn

SV - SPAn

ON

ON

SV

PV

SV - SPAn

SV + SPAn

ON

Positive SPAn

Negative SPAn

Difl

Minimum

Differential

(diFerential

Low)

SPAn positivo SPAn negativo

SV

PV

SV - SPAn

ON

SV

PV

SV - SPAn

ON

Difk

Maximum

Differential

(diFerential

High)

SV

SV + SPAn

ON

SV

PV

SV + SPAn

ON

Positive SPAn

Negative SPAn

Ierr

Sensor Break

(input Error)

Activated when the input signal of PV is

interrupted, out of the range limits or

Pt100 in short-circuit.

End.T

End of Level Activate at the end of the level time.

Rs

Event

(ramp and

Soak)

Can be activated at a specific segment

of program.

Table 4 – Alarm functions

Where SPAn refers to Setpoints of Alarm SPA1 and SPA2.

PROBLEMS WITH THE CONTROLLER

Connection errors and inadequate programming are the most common

errors found during the controller operation. A final revision may avoid

loss of time and damages. The controller displays some messages to

help the user identify problems.

: Sensor measuring temperature below the specified

minimum.

: Sensor measuring temperature above the specified

maximum.

: Controller failure or sensor error, examples: Thermocouple

open, Pt100 open in short circuit or poorly connected.

If the “Error” message persists after analysis of the

installation, contact manufacturer informing equipment’s

Serial Number.

FINDING THE CONTROLLER’S VERSION AND SERIAL NUMBER
When the controller is turned on, it shows on its displays for three

seconds its version (review). To see the serial number turn the

controller on holding the

key.

This information is necessary for eventual contact with the controller’s

manufacturer.

SPECIFICATIONS

DIMENSIONS: ........................................ 48 x 48 x 110 mm (1/16 DIN)

........................................................... Approximate Weight: 150 g

CUTOUT IN THE PANEL: .................. 45.5 x 45.5 mm (+0.5 -0.0 mm)
POWER SUPPLY: .................... 100 to 240 Vac/dc (±10 %), 50/60 Hz

Optionally: ....................................................... 24 Vdc/ac (±10 %)

Consumo máximo: ............................................................... 6 VA

ENVIRONMENTAL CONDITIONS:

Operation Temperature: ................................................ 5 to 50 °C
Relative Humidity: .......................................... 80 % max. up 30 ºC

For temperatures above 30 ºC, reduce 3 % for each ºC
Internal Use; Category of installation II, Degree of pollution 2;

altitude < 2000 m.

INPUT .......................... Thermocouples, Pt100 (according to Table 1)

Internal Resolution: ................................... 32767 levels (15 bits)
Resolution of Display: ...... 12000 levels (from -1999 up to 9999)
Rate of input reading: .................................. up to 55 per second
Precision: .. Thermocouples J, K, T, E: 0.25 % of the span ±1 ºC

.................. Thermocouples N, R, S, B: 0.25 % of the span ±3 ºC

............................................................... Pt100: 0.2 % of the span

Input Impedance: ................ Pt100 and thermocouples: >10 MΩ
Measurement of Pt100: ............... Three wires type, (α=0.00385)

with compensation for cable length, excitation current of 0.170 mA.
All input and output types are factory-calibrated. Thermocouples

according to standard NBR 12771 / 99, RTD’s NBR 13773 / 97;

OUTPUTS

OUTA / OUTC .......................... Relay SPST-NA: 1.5 A / 240 Vac,

...................................... General use, resistive load; 100 k cycles
OUTB ......................... Voltage pulse for SSR, 12 V max. / 20 mA
OUTD (RPR/RRR) .........Relay SPDT: 3 A / 250 Vac, general use
OUTD (RAR) ................................................. 0-20 mA or 4-20 mA

550 Ω max. 31000 levels, Isolated

ELECTROMAGNETIC COMPATIBILITY:
........................................ EN 61326-1:1997 and EN 61326-1/A1:1998
SAFETY: ........................... EN61010-1:1993 and EN61010-1/A2:1995
FRONT PANEL: IP65, POLYCARBONATE UL94 V-2;
CASE: IP30, ABS+PC UL94 V-0;
STARTS UP OPERATION AFTER 3 SECONDS CONNECTED TO

THE POWER SUPPLY.

MODEL IDENTIFICATION

The sticker on the controller presents the identification of the model, as

described below.
N480 D - A - B
Where A =

RP: OUTA: Relay; OUTB: Pulse

RPR: OUTA: Relay; OUTB: Pulse; OUTD: Relay

RAR: OUTA: Relay; OUTB: Pulse; OUTD: 0-20 / 4-20 mA

RRR: OUTA: Relay; OUTB: Pulse; OUTC: Relay; OUTD: Relay

Where B= ............................................... 24V for power supply 24 Vdc/ac

............................................ blank: power supply 100~240 Vac/dc

Advertising