Operation – NOVUS N1020 User Manual

Page 3

Advertising
background image

N1020 Temperature Controller

NOVUS AUTOMATION

3/8

The initial blocking is useful, for instance, when one of the alarms is
configured as a minimum value alarm, causing the activation of the
alarm soon upon the process start-up, an occurrence that may be
undesirable.
The initial blocking is disabled for the sensor break alarm function.

RAMP AND SOAK FUNCTION

When the parameter Rate is configured, the N1020 performs a
gradual SV increase from the current PV value to the temperature
value set in SV. The user defines the rate of rise in degrees per
minute
at the Rate prompt. When SV is reached, the temperature
is leveled at this point for 1 to 9999 minutes as programmed in the
T1me prompt. Setting 0 (zero) at T1me defines an infinite length soak

profile.

Soak

Temperature

PV

Ramp

Time

SP

Fig. 02 - Ramp to Soak Function

The Ramp function will work whenever the controller is powered on,
the rvn parameter is set to YES or the SP variable is changed.
To disable the ramp function, set Rate = 0.0
After a power failure the controller will resume ramp generation at the
current value of PV.

TIMER FUNCTION

The N1020 embeds a timer function (decreasing) for applications that
require particular process duration.
Once defined the time interval in the T1me parameter, the timer will

START when:

When PV reaches the temperature programmed in the SP
parameter.

When enabling the control (RUN = YES).

By pressing the F key when configured to Timer reset mode (the
timer is reloaded with the T1me parameter and restarts counting).

By pressing the F key in ON/OFF mode stops the timer counting;
pressing it again, resumes the counting.

When the timer expires, the two possible actions can be:

Disables de control (RUN→ NO) or

Activate the alarm.

FUNCTIONS FOR THE F KEY

The F key on the frontal keypad is meant for special commands, as
follows:

Enable outputs (identically to the RUN parameter).

Timer reset: - reloads the timer and initiates a new time
counting.

Timer ON/OFF. Timer holds or resumes counting each time
the F key is pressed.
Keeping the F key pressed for 3 seconds resets the timer
(reloads the timer to the value set in T1me), initiating a new

time counting.

Note: when the F key is configured as RUN = YES/NO (RUN =

f.key

), the controller outputs are born disabled after powers up.

SOFT-START
The Soft-start function is generally used in processes that require
slow start-up, where the instantaneous application of 100% of the
available power to the load may cause damages to parts of the
system.
In order to disable this function, the soft-start parameter must be
configured with 0 (zero).

OFFSET
Allows fine trimming the PV indication to compensate for sensor
errors. Default value: zero.

SERIAL COMMUNICATION

For full documentation download the Registers Table N1020 for
Serial Communication
on our web site

www.novusautomation.com

.

Fig. 02-a – Serial Communications Conections

OPERATION

The controller’s front panel, with its parts, can be seen in the Fig. 03:

Fig. 03 - Identification of the parts referring to the front panel

Display: Displays the current value of PV. When configuring a
parameter, the display alternates between the parameter prompt and
its value (the parameter value is shown with a light blinking to
differentiate it from the parameter prompt).
The display contains also the signs AT, OUT, RUN ALM and COM:

AT Indicator: Stays ON while the controller is in tuning process.
OUT Indicator: For relay or pulse control output; it reflects the
actual state of the output.
RUN Indicator: Indicates that the controller is active, with the
control output and alarms enabled. (RUN=YES).
ALM Indicator: Signalize the occurrence of alarm condition. It
lights when either alarm is active.
COM Indicator: Flashes when there is RS485 activity.

P Key: Used to walk through the menu parameters.

Increment key and

Decrement key: allow altering the

values of the parameters.

F Key: accesses special functions: RUN (toggles YES/NO) and the

two modes of timer control.

STARTUP
When the controller is powered up, it displays its firmware version for
3 seconds, after which the controller starts normal operation. The
value of PV is then displayed and the outputs are enabled.
In order for the controller to operate properly in a process, its
parameters need to be configured first, such that it can perform
accordingly to the system requirements. The user must be aware of
the importance of each parameter and for each one determine a valid
condition.
The parameters are grouped in levels according to their functionality
and operation easiness. The 5 levels of parameters are:

1 – Operation

2 – Tuning

3 – Alarms

4 – Configuration

5 – Calibration

The P key is used for accessing the parameters within a level.

Advertising