2

0023

Serial

number H

Serial Number High (Upper display).

Range: 0 to 9999. Read only.

0024

Serial

number L

Serial Number Low (Lower display).

Range: 0 to 9999. Read only.

0025

SV

Control Setpoint (Prompt Setpoint).

Range: from spll to spkl.

0026

spll

Setpoint Low limit.

Range: minimum value depends on the input type selected

in type (see Table 1) to spkl.

0027

spkl

Setpoint High limit.

Range: minimum value is spll and maximum depends on

the input type selected in type (see Table 1).

0028

Reserved

Internal use.

0029

offs

Offset value of PV(Process value).

Range: from spll to spkl.

0030

dppo

PV decimal point position

Range: 0 to 3

0

0.000; 1

00.00; 2

000.0; 3

0000

0031

Sp.a1

Alarm 1 Setpoint.

Range: From spll to spkl for non differential; and

spkl

- spll for differential alarm.

0032

Sp.a2

Alarm 2 Setpoint. Range: same as in spa1.

0033

Sp.a3

Alarm 3 Setpoint. Range: same as in spa1.

0034

Sp.a4

Alarm 4 Setpoint. Range: same as in spa1.

0035

Fva1

Alarm 1 Function. Range: 0 to 8

0

off

1

ierr

2

T.END

3

rs

4

lo

5

ki

6

dif

7

difl;

8

difk;

0036

Fva2

0037

Fva3

0038

Fva4

0039

Kya1

Alarm 1 Hysteresis. Range: 0 to 9999 (0.00 to 99.99%)

0040

Kya2

Alarm 2 Hysteresis. Range: same as in kya1.

0041

Kya3

Alarm 3 Hysteresis. Range: same as in kya1.

0042

Kya4

Alarm 4 Hysteresis. Range: same as in kya1.

0043

type

PV input type:

0 = J
1 = K
2 = T
3 = N
4 = R
5 = S
6 = B
7 = E
8 = Pt100
9 = 0-20 mA
10 = 4-20 mA
11 = 0-50 mV
12 = 0-5 V
13 = 0-10 V

0044

addr

Communication slave address. Range: 1 to 247

0045

bavd

Communication Baud-Rate:

0

1200;1

2400;2

4800;3

9600; 4

19200;

5

38400; 6

57600; 7

115200;

0046

avto

Control Mode. Range: 0

manual; 1

automatic.

0047

rvn

Enable control. Range: 0

no; 1

yes.

0048

act

Control action. Range: 0

direct; 1

reverse.

0049

atvn

Auto tune enable:

0= off;1= Fast; 2= Full; 3= Self; 4= rSLF; 5= tGHt;

0050

Bla1

Alarm power-up inhibit. Range: 0

no; 1

yes.

0051

Bla2

0052

Bla3

0053

Bla4

0054

Key

Key press remote action. Range: 0 to 9

1: tecla P
2: tecla

4: tecla

8: tecla B
9: teclas P e B

0062

A1t1

Alarm 1 Time 1. Range: 0 to 6500s.

Refer to operation manual for more details.

0063

A1t2

Alarm 1 Time 2 (in seconds).

Range: same as in a1t1.

0064

A2t1

Alarm 2 Time 1 (in seconds).

Range: same as in a1t1.

0065

A2t2

Alarm 2 Time 2 (in seconds).

Range: same as in a1t1.

0066

sfst

Soft-Start time (in seconds).

Range: 0 to 9999

0067

vnit

Temperature unit. Range: 0 to 1.

0



C; 1



F.

0068

bias

Bias. Range: -100 to +100%.

0070

R&S

Segment

Ramp and Soak segment being executed (read only).

Range: 0 to 9.

0071

Pr n

Ramp and Soak segment to be viewed or edited.

Range: 1 to 20.

0072

E pr

Ramp and Soak segment to be executed.

Range: 0 to 20.

0073 Remaining time

R&S

Indicates the remaining time of the Ramp and Soak
segment.

0074

Sqrt

Square root of a linear input.

Range: 0->Disable;1->Enable.

0075

Calibration PV

Low

Enter the low input value currently applied in the PV input
for calibration purposes.

0076

Calibration PV

High

Enter the high input value currently applied in the PV input
for calibration purposes.

0077

Calib. remote

SP Low

Enter the low input value currently applied in the remote
setpoint input for calibration purposes.

0078

Calib. remote

SP High

Enter the high input value currently applied in the remote
setpoint input for calibration purposes.

0081

FLSH

Enables the top display blinking as a function of the
selected alarm:

0-> Disable
1-> Enable to alarm 1
2-> Enable to alarm 2
3-> Enable to alarm 1 and 2

0086

Rstr

Restores original default calibration.

Range: 0 to 1; 0-> do not restore; 1-> restore calibration